Sterling 30RA010-055 Fault Codes, •P50: FAULT HISTORY — Last 8 faults, •P51: SOFTWARE version

Models: 30RA010-055

1 100
Download 100 pages 44.39 Kb
Page 71
Image 71

Table 37 — Fault Codes

FAULT CODE

DESCRIPTION

SOLUTION

AF

High Temperature Fault: Ambient temperature is too high;

Check cooling fan operation

 

Cooling fan has failed (if equipped).

 

CF

Control Fault: A blank EPM, or an EPM with corrupted data

Perform a factory reset using Parameter 48 —

 

has been installed.

PROGRAM SELECTION.

cF

Incompatibility Fault: An EPM with an incompatible parame-

Either remove the EPM or perform a factory

 

ter version has been installed.

reset (Parameter 48) to change the parameter

 

 

version of the EPM to match the parameter

 

 

version of the drive.

CL

CURRENT LIMIT: The output current has exceeded the

Check for loose electrical connections.

 

CURRENT LIMIT setting (Parameter 25) and the drive is

Check for faulty condenser fan motor.

 

reducing the output frequency to reduce the output current.

Check Parameter P25 from Table 38 is set cor-

 

If the drive remains in CURRENT LIMIT too long, it can trip

rectly.

 

into a CURRENT OVERLOAD fault (PF).

 

GF

Data Fault: User data and OEM defaults in the EPM are

Restore factory defaults P48, see section

 

corrupted.

above. If that does not work, replace EPM.

HF

High DC Bus Voltage Fault: Line voltage is too high; Decel-

Check line voltage — set P01 appropriately

 

eration rate is too fast; Overhauling load.

 

JF

Serial Fault: The watchdog timer has timed out, indicating

Check serial connection (computer)

 

that the serial link has been lost.

Check settings for PXX.

 

 

Check settings in communication software to

 

 

match PXX.

LF

Low DC Bus Voltage Fault: Line voltage is too low.

Check line voltage — set P01 appropriately

OF

Output Transistor Fault: Phase to phase or phase to ground

Reduce boost or increase acceleration values.

 

short circuit on the output; Failed output transistor; Boost

If unsuccessful, replace drive.

 

settings are too high; Acceleration rate is too fast.

 

PF

Current Overload Fault: VFD is undersized for the applica-

Check line voltage — set P01 appropriately

 

tion; Mechanical problem with the driven equipment.

Check for dirty coils

 

 

Check for motor bearing failure

SF

Single-phase Fault: Single-phase input power has been

Check input power phasing

 

applied to a three-phase drive.

 

F1

EPM Fault: The EPM is missing or damaged.

 

F2-F9, Fo

Internal Faults: The control board has sensed a problem

Consult factory

Drive display = 60.0 even though it

Feedback signal is above set point

Check for proper set point

is cold outside and it should be run-

 

Check liquid line pressure

ning slower

 

 

Drive display = ‘---’ even though

Start jumper is missing

Replace start jumper. See section above

drive should be running

 

 

Drive display = 8.0 even though fan

Feedback signal is below set point and fan is at minimum

Check for proper set point

should be running faster

speed

Check liquid line pressure

VFD flashes 57 and LCS

Feedback or speed signal lost. Drive will operate at 57 Hz

In stand alone mode: Check transducer wiring

 

until reset or loss of start command. Resetting requires

and feedback voltage. Feedback voltage dis-

 

cycling start command (or power).

played on P-69. Pin 6 should be 5 v output.

 

 

Pin 5 (feedback) should be somewhere

 

 

between 0 and 5 v.

Manual Reset — If fault condition has been removed, cycle power to the chiller to reset the VFD.

Troubleshooting — Troubleshooting the Motormaster® V control requires a combination of observing system operation and VFD information. The drive provides 2 kinds of trouble- shooting modes: a status matrix using the 3-digit display (P57, P58) and real time monitoring of key inputs and outputs. The collective group is displayed through parameters 50-60 and all values are read-only.

P50: FAULT HISTORY — Last 8 faults

P51: SOFTWARE version

P52: DC BUS VOLTAGE — in percent of nominal. Usually rated input voltage x 1.4

P53: MOTOR VOLAGE — in percent of rated output voltage

P54: LOAD — in percent of drives rated output current rating

P55: VDC INPUT — in percent of maximum input: 100 will indicate full scale which is 5 v

P56 4-20 mA INPUT — in percent of maximum input. 20% = 4 mA, 100% = 20 mA

Manual Starter Trip — If the VFD manual starter (MS-FC- HS, MS-FC-A1 or MS-FC-B1 depending on model) trips, locate the inrush current protectors (3 round black disks per motor) and verify their resistance. For units operating at 208 v or 230 v, these devices should measure approximately 7 ohms. For all other voltages, they should measure approximately 20 ohms. Check value with mating plug disconnected, power to chiller off and at ambient temperature (not hot immediately after stopping VFD). These are standard resistances at 77 F (25 C). Resistance values decrease at higher temperatures and increase at lower temperatures.

71

Page 71
Image 71
Sterling 30RA010-055 manual Fault Codes, •P50: FAULT HISTORY — Last 8 faults, •P51: SOFTWARE version