Sterling 30RA010-055 Thermistor Designations, Status Switches, Output Relays, Operating Data

Models: 30RA010-055

1 100
Download 100 pages 44.39 Kb
Page 4
Image 4
Table 2 — Thermistor Designations

At each system element, the shields of its communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the commu- nication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppressor in each building where the cable enters or exits the building (one point per building only). To connect the unit to the network:

1.Turn off power to the control box.

2.Cut the SCN wire and strip the ends of the red (+), white (ground), and black (–) conductors. (Substitute appropri- ate colors for different colored cables.)

3.Connect the red wire to (+) terminal on TB3 of the plug, the white wire to COM terminal, and the black wire to the

(–) terminal.

4.The RJ14 SCN connector on TB3 can also be used, but is only intended for temporary connection (for example, a laptop computer running Service Tool).

IMPORTANT: A shorted SCN bus cable will prevent some routines from running and may prevent the unit from start- ing. If abnormal conditions occur, unplug the connector. If conditions return to normal, check the SCN connector and cable. Run new cable if necessary. A short in one section of the bus can cause problems with all system elements on the bus.

Table 2 — Thermistor Designations

THERMISTOR

PIN

 

CONNECTION

THERMISTOR INPUT

NO.

 

 

POINT

 

 

 

 

T1

 

J8-13,14 (MBB)

Cooler Leaving Fluid

T2

 

J8-11,12 (MBB)

Cooler Entering Fluid

T7

 

J8-1,2 (MBB)

Circuit A Return Gas

 

 

Temperature (Accessory)

 

 

 

T8

 

J8-3,4 (MBB)

Circuit B (032-055 only) Return

 

 

Gas Temperature (Accessory)

 

 

 

T9

 

J8-7,8 (MBB)

Outdoor-Air Temperature

 

 

Sensor

 

 

 

T10

 

J8-5,6 (MBB)

Accessory Remote Space

 

TB5-5,6

Temperature Sensor or

 

 

 

Dual LWT Sensor

 

LEGEND

 

LWT — Leaving Water Temperature

 

MBB — Main Base Board

 

Table 3 — Status Switches

STATUS

PIN CONNECTION

SWITCH

POINT

Chilled Water Pump 1

J7-1,2

Chilled Water Pump 2

J7-3,4

Remote On/Off

TB5-9,10

Cooler Flow Switch

J7-9,10

Compressor Fault Signal, A1

J9-11,12

Compressor Fault Signal, A2

J9-5,6

Compressor Fault Signal, B1

J9-8,9

Compressor Fault Signal, B2

J9-2,3

Table 4 — Output Relays

RELAY

DESCRIPTION

NO.

 

K1

Energize Compressor A1 (010-030)

Energize Compressor A1 and Condenser Fan A1 (032-055)

 

K2

Energize Compressor B1 and Condenser Fan B1 at Low

Speed (032-040)

 

Energize Compressor B1 and Condenser Fan B1 (042-055)

K3

Energize Chilled Water Pump 1 Output

K4

Energize Chilled Water Pump 2 Output

K5

Energize Compressor A2 (all but 010, 015 60Hz)

K6

Energize Compressor B2 (042-055 only)

K7

Alarm Relay

K8

Cooler/Pump Heater

K9

Energize Condenser Fan at Low Speed (010-018)

Energize Condenser Fan A1 (022-030)

 

Energize Condenser Fan A2 (032-055)

 

Energize Condenser Fan at High Speed (010-018)

K10

Energize Condenser Fan A2 (022-030)

Energize Condenser Fan B1 at High Speed (032-040)

 

 

Energize Condenser Fan B2 (042-055)

K11

Minimum Load Valve

Table 5 — SCN Communication Bus Wiring

MANUFACTURER

PART NO.

Regular Wiring

Plenum Wiring

 

Alpha

1895

American

A21451

A48301

Belden

8205

884421

Columbia

D6451

Manhattan

M13402

M64430

Quabik

6130

OPERATING DATA

Sensors — The electronic control uses 3 to 6 thermistors to sense temperatures for controlling chiller operation. See Table 2. These sensors are outlined below. Thermistors T1, T2, T9 and accessory suction gas temperatures (T7,T8) are 5 kat 77 F (25 C) and are identical in temperature versus resistance and voltage drop performance. Thermistor T10 is 10 kat 77 F (25 C) and has a different temperature vs. resistance and voltage drop performance. See Thermistors section for temperature-resistance-voltage drop characteristics.

T1 — COOLER LEAVING FLUID SENSOR — On 30RA010- 030 sizes, this thermistor is installed in a friction fit well at the bottom of the brazed-plate heat exchanger on the control box side. For 30RA032-055 sizes, this thermistor is installed in a well in the factory-installed leaving fluid piping coming from the bottom of the brazed-plate heat exchanger opposite the control box side.

T2 — COOLER ENTERING FLUID SENSOR —On 30RA010- 030 sizes, this thermistor is installed in a friction fit well at the top of the brazed-plate heat exchanger on the control box side. For 30RA032-055 sizes, this thermistor is installed in a well in the factory-installed entering fluid piping coming from the top of the brazed-plate heat exchanger opposite the control box side.

T7,T8 — COMPRESSOR RETURN GAS TEMPERA- TURE SENSOR (ACCESSORY) — A well for this sensor is factory installed in each circuit's suction line. If desired, a 5 kthermistor (Sterling part number HH79NZ029) can be installed in this well and connected to the Main Base Board as shown in Table 2. Use the Scrolling Marquee display to con- figure the sensor (Configuration mode, sub-mode OPT1 — enable item RG.EN).

T9 — OUTDOOR-AIR TEMPERATURE SENSOR — This sensor is factory-installed on a bracket at the left side of compressor A1 on 30RA010-030 models. For models 30RA032-055, it is installed behind the panel below the control box center door.

4

Page 4
Image 4
Sterling 30RA010-055 Thermistor Designations, Status Switches, Output Relays, SCN Communication Bus Wiring, Operating Data