Sterling 30RA010-055 Appendix B, Factory Settings For Compressor, Fan, Pump, And Manual Starters

Models: 30RA010-055

1 100
Download 100 pages 44.39 Kb
Page 89
Image 89

APPENDIX B

FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP,

AND MANUAL STARTERS

 

 

 

OVERLOAD

OVERLOAD

MANUAL

MANUAL

MANUAL

 

 

MANUAL STARTER

 

UNIT

 

 

RELAY (CA1)

RELAY (CA2)

(CWP1, CWP2) SETTINGS

VOLTAGE

VOLTAGE

STARTER

STARTER

STARTER

SIZE

SETTING FOR

SETTING FOR

 

FOR PUMP OPTIONS

 

V-PH-Hz

SERIES

SETTING FOR

SETTING FOR

SETTING FOR

 

 

30RA

COMPRESSOR

COMPRESSOR

(Model Number Position 9)

 

 

FANS FC-HS/LS

FANS FC-A1/A2

CHC (Heaters)

 

 

 

A1

A2

A/F

 

B/G

C/H

D/J

 

E/K

 

 

 

 

 

 

 

 

 

575-3-60

-100

15.5

3.6

1.8

1.9

 

2.5

2.5

3.6

 

 

380-3-60

-200

24.2

5.5

1.8

2.9

 

3.7

3.7

5.4

 

 

230-3-60

-400

37.1

9.1

2.5

4.8

 

6.2

6.2

8.9

 

010

208/230-3-60

-500

41.2

10.1

2.5

5.3

 

7.0

7.0

9.8

 

 

460-3-60

-600

19.2

4.6

1.8

2.8

 

3.1

3.1

4.4

 

 

230-3-50

-800

40.9

7.6

2.5

3.4

 

4.8

4.8

6.1

 

 

380/415-3-50

-900

23.8

4.6

1.8

2.0

 

2.9

2.9

3.7

 

 

575-3-60

-100

22.7

3.6

1.8

1.9

 

2.5

2.5

3.6

 

 

380-3-60

-200

36.1

5.5

1.8

2.9

 

3.7

3.7

5.4

 

 

230-3-60

-400

52.6

9.1

2.5

4.8

 

6.2

6.2

8.9

 

015

208/230-3-60

-500

58.4

10.1

2.5

5.3

 

7.0

7.0

9.8

 

 

460-3-60

-600

28.6

4.6

1.8

2.8

 

3.1

3.1

4.4

 

 

230-3-50

-800

31.1

31.1

7.6

2.5

3.4

 

4.8

4.8

6.1

 

 

380/415-3-50

-900

17.2

17.2

4.6

1.8

2.0

 

2.9

2.9

3.7

 

 

575-3-60

-100

13.6

13.6

3.6

1.8

1.9

 

2.5

2.5

3.6

 

 

380-3-60

-200

21

21

5.5

1.8

2.9

 

3.7

3.7

5.4

 

 

230-3-60

-400

31.9

31.9

9.1

2.5

4.8

 

6.2

6.2

8.9

 

018

208/230-3-60

-500

35.4

35.4

10.1

2.5

5.3

 

7.0

7.0

9.8

 

 

460-3-60

-600

16.9

16.9

4.6

1.8

2.8

 

3.1

3.1

4.4

 

 

230-3-50

-800

33.7

33.7

7.6

2.5

3.4

 

4.8

4.8

6.1

 

 

380/415-3-50

-900

18.7

18.7

4.6

1.8

2.0

 

2.9

2.9

3.7

 

 

575-3-60

-100

14.6

19.9

2.3

1.8

1.9

 

2.5

2.5

3.6

 

 

380-3-60

-200

22.7

31.7

3.5

1.8

2.9

 

3.7

3.7

5.4

 

 

230-3-60

-400

35.3

44

5.8

2.5

4.8

 

6.2

6.2

8.9

 

022

208/230-3-60

-500

39.2

49

7.0

2.5

5.3

 

7.0

7.0

9.8

 

 

460-3-60

-600

17.5

24.2

2.9

1.8

2.8

 

3.1

3.1

4.4

 

 

230-3-50

-800

40.9

40.9

4.6

2.5

3.4

 

4.8

4.8

6.1

 

 

380/415-3-50

-900

23.8

23.8

3.7

1.8

2.0

 

2.9

2.9

3.7

 

 

575-3-60

-100

19.9

19.9

2.3

1.8

1.9

 

2.5

2.5

3.6

 

 

380-3-60

-200

31.7

31.7

3.5

1.8

2.9

 

3.7

3.7

5.4

 

 

230-3-60

-400

44

44

5.8

2.5

4.8

 

6.2

6.2

8.9

 

025

208/230-3-60

-500

49

49

7.0

2.5

5.3

 

7.0

7.0

9.8

 

 

460-3-60

-600

24.2

24.2

2.9

1.8

2.8

 

3.1

3.1

4.4

 

 

230-3-50

-800

49.9

49.9

4.6

2.5

3.4

 

4.8

4.8

6.1

 

 

380/415-3-50

-900

29

29

3.7

1.8

2.0

 

2.9

2.9

3.7

 

 

575-3-60

-100

22.7

22.7

2.3

1.8

1.9

 

2.5

2.5

3.6

 

 

380-3-60

-200

36.1

36.1

3.5

1.8

2.9

 

3.7

3.7

5.4

 

030

230-3-60

-400

52.6

52.6

5.8

2.5

4.8

 

6.2

6.2

8.9

 

 

208/230-3-60

-500

58.4

58.4

7.0

2.5

5.3

 

7.0

7.0

9.8

 

 

460-3-60

-600

28.6

28.6

2.9

1.8

2.8

 

3.1

3.1

4.4

 

89

Page 89
Image 89
Sterling 30RA010-055 manual Appendix B, Factory Settings For Compressor, Fan, Pump, And Manual Starters