Sterling 30RA010-055 ALARMDEF Alarm Definition Table, BRODEFS Broadcast POC Definition Table

Models: 30RA010-055

1 100
Download 100 pages 44.39 Kb
Page 79
Image 79

ALARMDEF (Alarm Definition Table)

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

Alarm Routing Control

00000000

00000000

 

ALRM_CNT

Equipment Priority

0 to 7

4

 

EQP_TYPE

Comm Failure Retry Time

1 to 240

10

min

RETRY_TM

Re-alarm Time

1 to 255

30

min

RE-ALARM

Alarm System Name

XXXXXXXX

CHILLER

 

ALRM_NAM

BRODEFS (Broadcast POC Definition Table)

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

SCN Time/Date Broadcast

Yes/No

No

 

SCNBC

SCN OAT Broadcast

Yes/No

No

 

OATBC

Global Schedule Broadcast

Yes/No

No

 

GSBC

SCN Broadcast Ack’er

Yes/No

No

 

SCNBCACK

Daylight Savings Start:

 

 

 

 

Month

1 to 12

4

 

STARTM

Week

1 to 5

1

 

STARTW

Day

1 to 7

7

 

STARTD

Minutes to Add

0 to 99

60

min

MINADD

Daylight Savings Stop

 

 

 

 

Month

1 to 12

10

 

STOPM

Week

1 to 5

5

 

STOPW

Day

1 to 7

7

 

STOPD

Minutes to Subtract

0 to 99

60

min

MINSUB

DISPLAY (Marquee Display SETUP)

DESCRIPTION

 

VALUE

DEFAULT

UNITS

POINT NAME

Service Password

nnnn

1111

 

PASSWORD

Password Enable

Enable/Disable

Enable

 

PASS_EBL

Metric Display

Off/On

Off

 

DISPUNIT

Language Selection

0

= ENGLISH

0

 

LANGUAGE

 

1

= FRANCAIS

 

 

 

 

2

= ESPANOL

 

 

 

 

3

= PORTUGUES

 

 

 

DUALCHIL (Dual Chiller Configuration Settings)

DESCRIPTION

VALUE

DEFAULT

UNITS

POINT NAME

LEAD/LAG

 

 

 

 

Lead/Lag Chiller Enable

Enable/Dsable

Dsable

 

LL_ENA

Master/Slave Select

Master/Slave

Master

 

MS_SEL

Slave Address

0 to 239

2

 

SLV_ADDR

Lead/Lag Balance Select

0 = None

0

 

LL_BAL

Lead/Lag Balance Delta

40 to 400

168

hours

LL_BAL_D

Lag Start Delay

0 to 30

5

minutes

LL_DELAY

Parallel Configuration

Yes

Yes

 

PARALLEL

79

Page 79
Image 79
Sterling 30RA010-055 manual ALARMDEF Alarm Definition Table, BRODEFS Broadcast POC Definition Table