OPTIONS1 (Options 1 Configuration)

DESCRIPTION

 

VALUE

DEFAULT

UNITS

POINT NAME

Cooler Fluid

1

= Water

1

 

FLUIDTYP

 

2

= Med. Brine

 

 

 

Minimum Load Vlv Select

No/Yes

No

 

MLV_FLG

Return Gas Sensor Enable

Dsable/Enable

Dsable

 

RGT_ENA

Motormaster Select

No/Yes

No

 

MTR_TYPE

Cooler Pump Control

Off/On

Off

 

CPC

Cooler Pump 1 Enable

No/Yes

No

 

PMP1_ENA

Cooler Pump 2 Enable

Dsable/Enable

Dsable

 

PMP2_ENA

Cooler Pmp Periodic Strt

No/Yes

No

 

PUMP_PST

Cooler Pump Select

0

= Automatic

0

 

PMP_SLCT

 

1

= Pump 1

 

 

 

 

2

= Pump 2

 

 

 

Cooler Pump Shutdown Dly

0 to 10

1

minutes

PUMP_DLY

Pump Changeover Hours

10 to 2000

500

hours

PMP_DLTA

EMM Module Installed

No/Yes

No

 

EMM_BRD

OPTIONS2 (Options 2 Configuration)

DESCRIPTION

 

VALUE

DEFAULT

UNITS

POINT NAME

Control Method

0

= Switch

0

 

CONTROL

 

2

= Occupancy

 

 

 

 

3

= SCN

 

 

 

Loading Sequence Select

1

= Equal Loading

1

 

SEQ_TYP

 

2

= Staged Loading

 

 

 

Lead/Lag Circuit Select

0

= Automatic

0

 

LEAD_TYP

 

1

= Circuit A Leads

 

 

 

 

2

= Circuit B Leads

 

 

 

Cooling Setpoint Select

0

= Single

0

 

CLSP_TYP

 

1

= Dual, remote switch controlled

 

 

 

 

2

= Dual SCN occupancy

 

 

 

 

3

= 4-20 mA input

 

 

 

Ramp Load Select

Enable/Dsable

Enable

 

RAMP_EBL

Heat Cool Select

Cool/Heat

Cool

 

HEATCOOL

High LCW Alert Limit

2 to 60

60.0

F

LCW_LMT

Minutes off time

0 to 15

0

min

DELAY

Deadband Multiplier

1.0 to 4.0

2.0

 

Z_GAIN

Ice Mode Enable

Enable/Dsable

Dsable

 

ICE_CNFG

Close Control Select

Enable/Dsable

Dsable

 

CLS_CTRL

Low Sound Mode Select

0

= Disabled

1

 

LS_MODE

 

1

= Fan only

 

 

 

 

2

= Capacity/Fans

 

 

 

Low Sound Start Time

00:00 to 23:59

00:00

 

LS_START

Low Sound End Time

00:00 to 23:59

00:00

 

LS_END

Low Sound Capacity Limit

0 to 100

100

%

LS_LIMIT

Enable Short Loop Gain

Enable/Dsable

Enable

 

SAGENABL