Sterling 30RA010-055 manual Alarm and Alert Codes cont

Models: 30RA010-055

1 100
Download 100 pages 44.39 Kb
Page 54
Image 54

Table 29 — Alarm and Alert Codes (cont)

ALARM/

ALARM

 

WHY WAS THIS

ACTION TAKEN

RESET

PROBABLE

ALERT

OR

DESCRIPTION

ALARM

BY CONTROL

METHOD

CAUSE

CODE

ALERT

 

GENERATED?

 

 

 

 

 

 

 

 

 

 

 

T093

Alert

Circuit B Suction

Voltage ratio more than

Circuit B shut down

Automatic

Transducer failure, poor

 

 

Pressure Transducer

99.9% or less than .5%.

 

 

connection to MBB, or wiring

 

 

Failure

 

 

 

damage/error.

T110

Alert

Circuit A Loss of Charge

If the compressors are off

Circuit not allowed to

Manual

Refrigerant leak or

 

 

 

and discharge pressure

start.

 

transducer failure

 

 

 

reading is < 10 psig for

 

 

 

 

 

 

30 sec.

 

 

 

 

 

 

 

 

 

 

T111

Alert

Circuit B Loss of Charge

If the compressors are off

Circuit not allowed to

Manual

Refrigerant leak or

 

 

 

and discharge pressure

start.

 

transducer failure

 

 

 

reading is < 10 psig for

 

 

 

 

 

 

30 sec.

 

 

 

 

 

 

 

 

 

 

T112

Alert

Circuit A High Saturated

Circuit saturated suction

Circuit shut down

Manual

Faulty Expansion valve,

 

 

Suction Temperature

temperature pressure

 

 

faulty suction pressure

 

 

 

transducer > 60 F (15.6 C)

 

 

transducer or high entering

 

 

 

for 5 minutes

 

 

fluid temperature.

T113

Alert

Circuit B High Saturated

Circuit saturated suction

Circuit shut down

Manual

Faulty Expansion valve,

 

 

Suction Temperature

temperature pressure

 

 

faulty suction pressure

 

 

 

transducer > 60 F (15.6 C)

 

 

transducer or high entering

 

 

 

for 5 minutes

 

 

fluid temperature.

T114

Alert

Circuit A Low Suction

Return gas sensor enabled

Circuit A shut down after

Automatic restart

Faulty expansion valve,

 

 

Superheat

and suction superheat is

pumpdown complete.

after first daily

faulty suction pressure

 

 

 

more than 10° F (5.6 C)

 

occurrence.

transducer, faulty suction gas

 

 

 

below the suction superheat

 

Manual restart

thermistor, circuit

 

 

 

set point for 5 minutes.

 

thereafter.

overcharged

T115

Alert

Circuit B Low Suction

Return gas sensor enabled

Circuit B shut down after

Automatic restart

Faulty expansion valve,

 

 

Superheat

and suction superheat is

pumpdown complete.

after first daily

faulty suction pressure

 

 

 

more than 10° F (5.6 C)

 

occurrence.

transducer, faulty suction

 

 

 

below the suction superheat

 

Manual restart

gas thermistor, circuit

 

 

 

set point for 5 minutes.

 

thereafter.

overcharged

T116

Alert

Circuit A Low Cooler

Mode 7 caused the com-

Circuit shut down

Manual

Faulty expansion valve, low

 

 

Suction Temperature

pressor to unload 6 consecu-

 

 

refrigerant charge, plugged

 

 

 

tive times with less than a

 

 

filter drier, faulty suction

 

 

 

30-minute interval between

 

 

pressure transducer, low

 

 

 

each circuit shutdown.

 

 

cooler fluid flow

T117

Alert

Circuit B Low Cooler

Mode 8 caused the com-

Circuit shut down

Manual

Faulty expansion valve, low

 

 

Suction Temperature

pressor to unload 6 consecu-

 

 

refrigerant charge, plugged

 

 

 

tive times with less than a

 

 

filter drier, faulty suction

 

 

 

30-minute interval between

 

 

pressure transducer, low

 

 

 

each circuit shutdown.

 

 

cooler fluid flow

T126

Alert

Circuit A High

SCT >Maximum condensing

Circuit shut down

Automatic, only

Faulty transducer/high

 

 

Discharge Pressure

temperature from operating

 

after first 3 daily

pressure switch, low/

 

 

 

envelope

 

occurrences.

restricted condenser

 

 

 

 

 

Manual reset

airflow

 

 

 

 

 

thereafter. Read-

 

 

 

 

 

 

ing from OAT sen-

 

 

 

 

 

 

sor (T9) must drop

 

 

 

 

 

 

5 F (2.8 C) before

 

 

 

 

 

 

restart

 

T127

Alert

Circuit B High

SCT >Maximum condensing

Circuit shut down

Automatic, only

Faulty transducer/high

 

 

Discharge Pressure

temperature from operating

 

after first 3 daily

pressure switch, low/

 

 

 

envelope

 

occurrences. Man-

restricted condenser

 

 

 

 

 

ual reset thereafter.

airflow

 

 

 

 

 

Reading from OAT

 

 

 

 

 

 

sensor (T9) must

 

 

 

 

 

 

drop 5 F (2.8 C)

 

 

 

 

 

 

before restart

 

T133

Alert

Circuit A Low Suction

Suction pressure below

Circuit shut down

Automatic

Faulty or plugged TXV, low

 

 

Pressure

15 psig for 8 seconds or

 

restart after first

refrigerant charge, TXV out

 

 

 

below 8 psig

 

daily occurrence.

of adjustment, liquid

 

 

 

 

 

Manual restart

line valve partially closed

 

 

 

 

 

thereafter.

 

T134

Alert

Circuit B Low Suction

Suction pressure below

Circuit shut down

Automatic

Faulty or plugged TXV, low

 

 

Pressure

15 psig for 8 seconds or

 

restart after first

refrigerant charge, TXV out

 

 

 

below 8 psig

 

daily occurrence.

of adjustment, liquid

 

 

 

 

 

Manual restart

line valve partially closed

 

 

 

 

 

thereafter.

 

54

Page 54
Image 54
Sterling 30RA010-055 manual Alarm and Alert Codes cont