III.Unit Start-Up (cont)

PRESS ESCAPE KEY TO DISPLAY ‘OPT1’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT2’. PRESS ENTER KEY.

RECORD CONFIGURATION INFORMATION BELOW.

OPTIONS2 (Options Configuration)

SUBMODE

ITEM

DISPLAY

DESCRIPTION

VALUE

OPT2

 

 

UNIT OPTIONS 2 CONTROLS

 

 

CTRL

X

CONTROL METHOD

 

 

SCNA

XXX

SCN ADDRESS

 

 

SCNB

XXX

SCN BUS NUMBER

 

 

BAUD

X

SCN BAUD RATE

 

 

LOAD

X

LOADING SEQUENCE SELECT

 

 

LLCS

X

LEAD/LAG CIRCUIT SELECT

 

 

LCWT

XX.X F

HIGH LCW ALERT LIMIT

 

 

DELY

XX

MINUTES OFF TIME

 

 

ICE.M

ENBL/DSBL

ICE MODE ENABLE

 

 

CLS.C

ENBL/DSBL

CLOSE CONTROL SELECT

 

 

LS.MD

X

LOW SOUND MODE SELECT

 

 

LS.ST

00:00

LOW SOUND START TIME

 

 

LS.ND

00:00

LOW SOUND END TIME

 

 

LS.LT

XXX %

LOW SOUND CAPACITY LIMIT

 

RSET (Reset Configuration Settings)

SUBMODE

ITEM

DISPLAY

DESCRIPTION

VALUE

RSET

 

 

RESET COOL TEMP

 

 

CRST

X

COOLING RESET TYPE

 

 

MA.DG

XX.X °F

4-20 - DEGREES RESET

 

 

RM.NO

XXX.X °F

REMOTE - NO RESET TEMP

 

 

RM.F

XXX.X °F

REMOTE - FULL RESET TEMP

 

 

RM.DG

XX.X °F

REMOTE - DEGREES RESET

 

 

RT.NO

XXX.X °F

RETURN - NO RESET TEMP

 

 

RT.F

XXX.X °F

RETURN - FULL RESET TEMP

 

 

RT.DG

XX.X °F

RETURN - DEGREES RESET

 

 

DMDC

X

DEMAND LIMIT SELECT

 

 

DM20

XXX %

DEMAND LIMIT AT 20 MA

 

 

SHNM

XXX

LOADSHED GROUP NUMBER

 

 

SHDL

XXX %

LOADSHED DEMAND DELTA

 

 

SHTM

XXX

MAXIMUM LOADSHED TIME

 

 

DLS1

XXX %

DEMAND LIMIT SWITCH 1

 

 

DLS2

XXX %

DEMAND LIMIT SWITCH 2

 

 

LLEN

ENBL/DSBL

LEAD/LAG CHILLER ENABLE

 

 

MSSL

SLVE/MAST

MASTER/SLAVE SELECT

 

 

SLVA

XXX

SLAVE ADDRESS

 

 

LLBL

X

LEAD/LAG BALANCE SELECT

 

 

LLBD

XXX

LEAD/LAG BALANCE DELTA

 

 

LLDY

XXX

LAG START DELAY

 

 

PARA

YES/NO

PARALLEL CONFIGURATION

 

CL-6

Page 98
Image 98
Sterling 30RA010-055 manual OPTIONS2 Options Configuration, RSET Reset Configuration Settings, III.Unit Start-Upcont, CL-6