Sterling 30RA010-055 manual Troubleshooting, Configuring Demand Limit

Models: 30RA010-055

1 100
Download 100 pages 44.39 Kb
Page 46
Image 46
Table 27 — Configuring Demand Limit

Table 27 — Configuring Demand Limit

MODE

KEYPAD

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM EXPANSION

COMMENT

ENTRY

ENTRY

 

 

 

 

 

 

CONFIGURATION

ENTER

DISP

ENTER

TEST

ON/OFF

Test Display LEDs

 

 

 

UNIT

ENTER

TYPE

X

Unit Type

 

 

 

OPT1

ENTER

FLUD

X

Cooler Fluid

 

 

 

OPT2

ENTER

CTRL

X

Control Method

 

 

 

RSET

ENTER

CRST

X

Cooling Reset Type

 

 

 

 

 

 

 

 

Default: 0

 

 

 

 

DMDC*

X

Demand Limit Select

0 = None

 

 

 

 

1 = Switch

 

 

 

 

 

 

 

2 = 4 to 20 mA Input

 

 

 

 

 

 

 

3 = SCN Loadshed

 

 

 

 

DM20

XXX %

Demand Limit at 20 mA

Default: 100%

 

 

 

 

Range: 0 to 100

 

 

 

 

 

 

 

 

 

 

 

SHNM

XXX

Loadshed Group

Default: 0

 

 

 

 

Number

Range: 0 to 99

 

 

 

 

 

 

 

 

 

 

SHDL

XXX%

Loadshed Demand

Default: 0%

 

 

 

 

Delta

Range: 0 to 60%

 

 

 

 

 

 

 

 

 

 

SHTM

XXX MIN

Maximum Loadshed

Default: 60 min.

 

 

 

 

Time

Range: 0 to 120 min.

 

 

 

 

 

 

 

 

 

 

DLS1

XXX %

Demand Limit

Default: 80%

 

 

 

 

Switch 1

Range: 0 to 100%

 

 

 

 

 

 

 

 

 

 

DLS2

XXX %

Demand Limit

Default: 50%

 

 

 

 

Switch 2

Range: 0 to 100%

 

 

 

 

 

 

*Seven items skipped in this example.

TROUBLESHOOTING

Complete Unit Stoppage and Restart — Possi- ble causes for unit stoppage and reset methods are shown be- low. (See Table 28 also.) Refer to Fig. 22-26 for Component Arrangement and Control Wiring Diagrams.

GENERAL POWER FAILURE — After power is restored, restart is automatic through normal MBB start-up.

UNIT ENABLE-OFF-REMOTE CONTACT SWITCH IS OFF — When the switch is OFF, the unit will stop immediate- ly. Place the switch in the ENABLE position for local switch control or in the REMOTE CONTACT position for control through remote contact closure.

CHILLED FLUID PROOF-OF-FLOW SWITCH OPEN — After the problem causing the loss of flow has been corrected, reset is manual by resetting the alarm with the Scrolling Mar- quee as shown in Table 24.

OPEN HIGH-PRESSURE SWITCH(ES) — Determine and correct the cause of the failure. The switch automatically resets, but the unit must be reset manually by resetting the alarm with the Scrolling Marquee as shown in Table 24.

OPEN COMPRESSOR INTERNAL THERMAL PRO- TECTION — This switch provides compressor over tempera- ture protection. Determine and correct the cause of the prob- lem. The switch resets automatically, but the unit must be reset manually resetting the alarm with the Scrolling Marquee as shown in Table 24.

OPEN 24-V CONTROL CIRCUIT BREAKER(S) — De- termine the cause of the failure and correct. Reset circuit break- er(s). Restart is automatic after MBB start-up cycle is com- plete.

COOLING LOAD SATISFIED — Unit shuts down when cooling load has been satisfied. Unit restarts when required to satisfy leaving fluid temperature set point.

THERMISTOR FAILURE — If a thermistor fails in either an open or shorted condition, the unit will be shut down. Replace T1, T2, or T9 as required. Unit restarts automatically, but must be reset manually by resetting the alarm with the Scrolling Marquee as shown in Table 24.

If unit stoppage occurs more than once as a result of any of the safety devices listed, determine and correct cause before attempting another restart.

LOW SATURATED SUCTION — Several conditions can lead to low saturated suction alarms and the chiller controls have several override modes built in which will attempt to keep the chiller from shutting down. Low fluid flow, low refrigerant charge and plugged filter driers are the main causes for this condition. To avoid permanent damage and potential freezing of the system, do NOT repeatedly reset these alert and/or alarm conditions without identifying and correcting the cause(s).

46

Page 46
Image 46
Sterling 30RA010-055 manual Troubleshooting, Configuring Demand Limit