Table 24 — Example of Reading and Clearing Alarms

Table 24 — Example of Reading and Clearing Alarms

SUB-MODE

KEYPAD

ITEM

ITEM EXPANSION

COMMENT

ENTRY

 

 

 

 

CRNT

ENTER

AXXX or TXXX

CURRENTLY ACTIVE ALARMS

ACTIVE ALARMS (AXXX) OR

ALERTS (TXXX) DISPLAYED.

 

 

 

 

 

CRNT

ESCAPE

 

 

 

 

 

NO

 

Use to clear active alarms/alerts

RCRN

ENTER

NO

 

NO Flashes

 

YES

 

Select YES

 

 

 

 

ENTER

NO

 

Alarms/alerts clear, YES changes to NO

 

 

 

Table 25A — 4-20 mA Reset

 

 

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM

 

COMMENT

ENTRY

EXPANSION

 

 

 

 

 

 

RSET

 

 

 

 

0

= no reset

 

 

 

 

COOLING RESET

1

= 4 to 20 mA input

 

ENTER

CRST

1

2

= Outdoor air temp

 

 

TYPE

 

 

 

 

3

= Return Fluid

 

 

 

 

 

 

 

 

 

 

4

= Space Temperature

 

 

CRT1

4.0

NO COOL RESET

Default: 125 F (51.7 C)

 

 

TEMP

Range: 0° to 125 F

 

 

 

 

 

 

CRT2

20.0

FULL COOL

Default: 0° F (–17.8 C)

 

 

RESET TEMP

Range: 0° to 125 F

 

 

 

 

 

 

DGRC

5.0 F

DEGREES COOL

Default: 0° F (0° C) Reset at 20 mA

 

 

(2.8 C)

RESET

Range: –30 to 30 F (–16.7 to 16.7 C)

 

 

 

NOTE: The example above shows how to configure the chiller for 4-20 mA reset. No reset will occur at 4.0 mA input, and a 5.0 F reset will occur at 20.0 mA. An EMM is required.

Table 25B — Menu Configuration of 4 to 20 mA Cooling Set Point Control

MODE

KEYPAD

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM

COMMENT

(RED LED)

ENTRY

 

ENTRY

 

 

EXPANSION

 

 

ENTER

DISP

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

 

OPT1

 

 

 

 

 

 

 

OPT2

 

 

 

 

 

CONFIGURATION

 

RSET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLCT

ENTER

CLSP

0

COOLING SETPOINT SELECT

 

 

 

 

 

 

 

 

ENTER

 

0

 

Scrolling Stops

 

 

 

 

 

 

 

 

 

ENTER

 

0

 

Flashing ‘0’

 

 

 

 

 

 

 

 

 

 

 

4

 

Select ‘4’

 

 

 

ENTER

 

4

 

Change Accepted

 

 

 

 

 

 