Table 7 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve

30RA UNIT SIZE

CONTROL

LOADING SEQ A

LOADING SEQ B

STEPS

% Displacement

Compressor

% Displacement

Compressor

 

 

 

010 (50/60 Hz)

1

69/ 71

A1*

2

100/100

A1

 

015 (60 Hz)

1

79

A1*

2

100

A1

 

015 (50 Hz)

1

28

A1*

2

50

A1

 

3

100

A1,A2

018 (50/60 Hz)

1

32/ 31

A1*

2

50/ 50

A1

 

3

100/100

A1,A2

022 (50/60 Hz)

1

27/ 35

A1*

2

42/ 50

A1

 

3

100/100

A1,A2

025 (50/60 Hz)

1

38/ 37

A1*

2

50/ 50

A1

 

3

100/100

A1,A2

030

1

39

A1*

2

50

A1

 

3

100

A1,A2

 

1

15

A1*

30

B1*

032

2

25

A1

40

B1

3

60

A1,A2

65

A1,B1

 

 

4

100

A1,A2,B1

100

A1,A2,B1

 

1

16/25

A1*

32/25

B1*

035 (50/60 Hz)

2

25/33

A1

40/33

B1

3

60/67

A1,A2

65/67

A1,B1

 

 

4

100

A1,A2,B1

100

A1,A2,B1

 

1

24

A1*

29

B1*

040

2

32

A1

37

B1

3

63

A1,A2

68

A1,B1

 

 

4

100

A1,A2,B1

100

A1,A2,B1

 

1

18

A1*

18

B1*

042

2

25

A1

25

B1

3

50

A1,B1

50

A1,B1

 

4

75

A1,A2,B1

75

A1,B1,B2

 

5

100

A1,A2,B1,B2

100

A1,A2,B1,B2

 

1

15

A1*

15

B1*

045 (60 Hz)

2

22

A1

22

B1

3

44

A1,B1

44

A1,B1

 

4

72

A1,A2,B1

72

A1,B1,B2

 

5

100

A1,A2,B1,B2

100

A1,A2,B1,B2

 

1

19

A1*

19

B1*

045 (50 Hz), 050

2

25

A1

25

B1

3

50

A1,B1

50

A1,B1

 

4

77

A1,A2,B1

77

A1,B1,B2

 

5

100

A1,A2,B1,B2

100

A1,A2,B1,B2

 

1

20

A1*

20

B1*

055

2

25

A1

25

B1

3

50

A1,B1

50

A1,B1

 

4

75

A1,A2,B1

75

A1,B1,B2

 

5

100

A1,A2,B1,B2

100

A1,A2,B1,B2

*Minimum Load Valve energized.

NOTE: These capacity steps may vary due to different capacity staging sequences.

19

Page 19
Image 19
Sterling 30RA010-055 manual 100/100