Sterling 30RA010-055 manual Sub-Mode, Keypad, Item, Display, Comment, OPT1, OPT2

Models: 30RA010-055

1 100
Download 100 pages 44.39 Kb
Page 32
Image 32
OPT1

Table 17 — Configuration Mode and Sub-Mode Directory (cont)

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM

 

COMMENT

ENTRY

EXPANSION

 

 

 

 

 

 

OPT1

 

 

 

 

 

UNIT OPTIONS 1 HARDWARE

 

 

 

 

 

 

FLUD

X

COOLER FLUID

Default: Water

 

 

ENTER

 

 

 

 

 

 

 

1

= Water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

= Medium Temperature Brine

 

 

 

 

MLV.S

YES/NO

MINIMUM LOAD VALVE SELECT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MMR.S

YES/NO

MOTORMASTER SELECT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RG.EN

ENBL/DSBL

RETURN GAS SENSOR ENABLE

Default: DISABLED

 

 

 

 

 

 

 

 

 

 

 

 

CPC

ON/OFF

COOLER PUMP CONTROL

Default: On

 

 

 

 

 

 

 

 

 

 

 

 

 

PM1E

YES/NO

COOLER PUMP 1 ENABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PM2E

YES/NO

COOLER PUMP 2 ENABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PM.P.S

YES/NO

COOLER PMP PERIODIC STRT

Default: No

 

 

 

 

 

 

 

 

 

 

 

 

PM.SL

X

COOLER PUMP SELECT

Default: Automatic

 

 

 

 

 

 

 

0

= Automatic

 

 

 

 

 

 

 

1

= Pump 1 Starts first

 

 

 

 

 

 

 

2

= Pump 2 Starts first

 

 

 

 

PM.DY

XX MIN

COOLER PUMP SHUTDOWN DLY

0 to 10 minutes, Default: 1 min.

 

 

 

 

 

 

 

 

 

 

 

 

PM.DT

XXXX HRS

PUMP CHANGEOVER HOURS

Default: 500 hours

 

 

 

 

 

 

 

 

 

 

 

 

ROT.P

YES/NO

ROTATE COOLER PUMPS NOW

User Entry

 

 

 

 

 

 

 

 

 

 

 

 

 

EMM

YES/NO

EMM MODULE INSTALLED

 

 

 

 

 

 

 

 

 

 

 

OPT2

 

 

 

 

 

UNIT OPTIONS 2 CONTROLS

 

 

 

 

 

 

CTRL

X

CONTROL METHOD

Default: Switch

 

 

ENTER

 

 

 

 

 

 

 

0

= Enable/Off/Remote Switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

= Occupancy

 

 

 

 

 

 

 

3

= SCN Control

 

 

 

 

SCNA

XXX

SCN ADDRESS

Default: 1

 

 

 

 

Range: 1 to 239

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCNB

XXX

SCN BUS NUMBER

Default: 0

 

 

 

 

Range: 0 to 239

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BAUD

X

SCN BAUD RATE

Default: 9600

 

 

 

 

 

 

 

1

= 2400

 

 

 

 

 

 

 

2

= 4800

 

 

 

 

 

 

 

3

= 9600

 

 

 

 

 

 

 

4

= 19,200

 

 

 

 

 

 

 

5

= 38,400

 

 

 

 

LOAD

X

LOADING SEQUENCE SELECT

Default: Equal

 

 

 

 

 

 

 

1

= Equal

 

 

 

 

 

 

 

2

= Staged

 

 

 

 

LLCS

X

LEAD/LAG CIRCUIT SELECT

Default: Automatic

 

 

 

 

 

 

 

1

= Automatic

 

 

 

 

 

 

 

2

= Circuit A Leads

 

 

 

 

 

 

 

3

= Circuit B Leads

 

 

 

 

LCWT

XX.X F

HIGH LCW ALERT LIMIT

Default: 60

 

 

 

 

Range: 2 to 60 °F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DELY

XX

MINUTES OFF TIME

Default: 0 Minutes

 

 

 

 

Range: 0 to 15 Minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ICE.M

ENBL/DSBL

ICE MODE ENABLE

Default: Disable

 

 

 

 

 

 

 

 

 

 

 

 

CLS.C

ENBL/DSBL

CLOSE CONTROL SELECT

Default: Disable

 

 

 

 

 

 

 

 

 

 

 

 

LS.MD

X

LOW SOUND MODE SELECT

Default: 0

 

 

 

 

 

 

 

0

= Mode Disable

 

 

 

 

 

 

 

1

= Fan Noise Only

 

 

 

 

 

 

 

2

= Fan/Compressor Noise

 

 

 

 

 

 

 

 

 

 

 

 

LS.ST

00:00

LOW SOUND START TIME

Default: 00:00

 

 

 

 

 

 

 

 

 

 

 

 

LS.ND

00:00

LOW SOUND END TIME

Default: 00:00

 

 

 

 

 

 

 

 

 

 

 

 

LS.LT

XXX %

LOW SOUND CAPACITY LIMIT

Default: 100%

 

 

 

 

Range: 0 to 100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RSET

 

 

 

 

 

RESET COOL TEMP

 

 

 

 

 

 

CRST

X

COOLING RESET TYPE

Default: No Reset

 

 

ENTER

 

 

 

 

 

 

 

0

= No Reset

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

= 4 to 20 mA Input

 

 

 

 

 

 

 

2

= Outdoor Air Temperature

 

 

 

 

 

 

 

3

= Return Fluid

 

 

 

 

 

 

 

4

= Space Temperature

 

 

 

 

MA.DG

XX.X F

4-20 - DEGREES RESET

Default: 0.0 F

 

 

 

 

Range: –30 to 30 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RM.NO

XXX.X °F

REMOTE - NO RESET TEMP

Default: 125 F (51.7 C)

 

 

 

 

Range: 0° to 125 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

Page 32
Image 32
Sterling 30RA010-055 manual Sub-Mode, Keypad, Item, Display, Comment, OPT1, OPT2