Sterling 30RA010-055 manual Sub-Mode, Keypad, Item, Display, Comment, Bcst

Models: 30RA010-055

1 100
Download 100 pages 44.39 Kb
Page 33
Image 33
BCST

Table 17 — Configuration Mode and Sub-Mode Directory (cont)

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM

 

COMMENT

ENTRY

EXPANSION

 

 

 

 

 

 

RSET (cont)

 

 

 

RM.F

XXX.X °F

REMOTE - FULL RESET TEMP

Default: 0.0° F (-17.8 C)

 

 

 

 

Range:

0° to 125 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RM.DG

XX.X °F

REMOTE - DEGREES RESET

Default: 0.0° F

 

 

 

 

Range: –30 to 30 F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT.NO

XXX.X F

RETURN - NO RESET TEMP

Default: 10.0 F (5.6 C)

 

 

 

 

Range:

0° to 125 F COOLER T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT.F

XXX.X F

RETURN - FULL RESET TEMP

Default: 0.0 F (0.0 C)

 

 

 

 

Range:

0° to 125 F COOLER T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT.DG

XX.X °F

RETURN - DEGREES RESET

Default: 0.0° F

 

 

 

 

Range: –30 to 30 F (–34.4 to -1.1 C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DMDC

X

DEMAND LIMIT SELECT

Default: None

 

 

 

 

 

 

 

0 = None

 

 

 

 

 

 

 

1 = Switch

 

 

 

 

 

 

 

2 = 4 to 20 mA Input

 

 

 

 

 

 

 

3 = SCN Loadshed

 

 

 

 

DM20

XXX %

DEMAND LIMIT AT 20 MA

Default:

100%

 

 

 

 

Range:

0 to 100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHNM

XXX

LOADSHED GROUP NUMBER

Default:

0

 

 

 

 

Range:

0 to 99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHDL

XXX %

LOADSHED DEMAND DELTA

Default:

0%

 

 

 

 

Range:

0 to 60%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHTM

XXX

MAXIMUM LOADSHED TIME

Default:

60 minutes

 

 

 

 

Range:

0 to 120 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DLS1

XXX %

DEMAND LIMIT SWITCH 1

Default:

80%

 

 

 

 

Range:

0 to 100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DLS2

XXX %

DEMAND LIMIT SWITCH 2

Default:

50%

 

 

 

 

Range:

0 to 100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LLEN

ENBL/DSBL

LEAD/LAG CHILLER ENABLE

Default: Disable

 

 

 

 

 

 

 

 

 

 

 

 

MSSL

SLVE/MAST

MASTER/SLAVE SELECT

Default: Master

 

 

 

 

 

 

 

 

 

 

 

 

 

SLVA

XXX

SLAVE ADDRESS

Default:

2

 

 

 

 

Range:

0 to 239

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LLBL

X

LEAD/LAG BALANCE SELECT

Default: Master Leads

 

 

ENTER

 

 

 

 

 

 

 

0 = Master Leads

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 = Slave Leads

 

 

 

 

 

 

 

2 = Automatic

 

 

 

 

LLBD

XXX

LEAD/LAG BALANCE DELTA

Default:

168 hours

 

 

 

 

Range:

40 to 400 hours

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LLDY

XXX

LAG START DELAY

Default:

5 minutes

 

 

 

 

Range:

0 to 30 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PARA

YES

PARALLEL CONFIGURATION

Default: YES (CANNOT BE CHANGED)

 

 

 

 

 

 

 

 

 

SLCT

 

 

 

 

 

SETPOINT AND RAMP LOAD

 

 

 

 

 

 

CLSP

X

COOLING SETPOINT SELECT

Default: Single

 

 

ENTER

 

 

 

 

 

 

 

0 = Single

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 = Dual Switch

 

 

 

 

 

 

 

2 = Dual SCN Occupied

 

 

 

 

 

 

 

3 = 4 to 20 mA Input (requires

 

 

 

 

 

 

 

EMM)

 

 

 

 

RL.S

ENBL/DSBL

RAMP LOAD SELECT

Default: Enable

 

 

 

 

 

 

 

 

 

 

 

 

 

CRMP

X.X

COOLING RAMP LOADING

Default:

1.0

 

 

 

 

Range:

0.2 to 2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCHD

XX

SCHEDULE NUMBER

Default:

1

 

 

 

 

Range:

1 to 99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Z.GN

X.X

DEADBAND MULTIPLIER

Default:

2.0

 

 

 

 

Range:

1.0 to 4.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SERV

 

 

 

 

 

SERVICE CONFIGURATION

 

 

 

 

 

EN.A1

ENBL/DSBL

ENABLE COMPRESSOR A1

Unit dependent

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EN.A2

ENBL/DSBL

ENABLE COMPRESSOR A2

Unit dependent

 

 

 

 

 

 

 

 

 

 

 

 

EN.B1

ENBL/DSBL

ENABLE COMPRESSOR B1

Unit dependent

 

 

 

 

 

 

 

 

 

 

 

 

EN.B2

ENBL/DSBL

ENABLE COMPRESSOR B2

Unit dependent

 

 

 

 

 

 

 

 

 

BCST

 

 

 

 

 

BROADCAST CONFIGURATION

 

 

 

 

 

T.D.BC

ON/OFF

SCN TIME/DATE BROADCAST

 

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OAT.B

ON/OFF

SCN OAT BROADCAST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G.S.BC

ON/OFF

GLOBAL SCHEDULE BROADCAST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BC.AK

ON/OFF

SCN BROADCAST ACK’ER

 

 

 

 

 

 

 

 

 

 

 

33

Page 33
Image 33
Sterling 30RA010-055 manual Sub-Mode, Keypad, Item, Display, Comment, Bcst