Service Test Mode and Sub-Mode Directory

III.Unit Start-Up (cont)

COMPONENT TEST

USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY ‘DISP’. PRESS ENTER AGAIN TO DISPLAY ‘TEST’ FOLLOWED BY ‘OFF’. PRESS ENTER TO STOP DISPLAY AT ‘OFF’ AND ENTER AGAIN SO ‘OFF’ DISPLAY FLASHES. ‘PASS’ AND ‘WORD’ WILL FLASH IF PASSWORD NEEDS TO BE ENTERED. PRESS ENTER TO DISPLAY PASSWORD FIELD AND USE THE ENTER KEY FOR EACH OF THE FOUR PASSWORD DIGITS. USE ARROW KEYS IF PASSWORD IS OTHER THAN STANDARD. AT FLASHING ‘OFF’ DISPLAY, PRESS THE UP ARROW KEY TO DISPLAY ‘ON’ AND PRESS ENTER. ALL LED SEGMENTS AND MODE LEDS WILL LIGHT UP. PRESS ESCAPE TO STOP THE TEST. PRESS ESCAPE TO RETURN TO THE ‘DISP’ DISPLAY. PRESS THE ESCAPE KEY AGAIN AND USE THE ARROW KEYS TO ILLU- MINATE THE SERVICE TEST LED. PRESS ENTER TO DISPLAY ‘TEST’. PRESS ENTER TO STOP DISPLAY AT ‘OFF’ AND ENTER AGAIN SO ‘OFF’ FLASHES. PRESS THE UP ARROW KEY AND ENTER TO ENABLE THE MANUAL MODE. PRESS ESCAPE AND DISPLAY NOW SAYS ‘TEST’ ‘ON’. REFER TO THE TABLE BELOW.

Service Test Mode and Sub-Mode Directory

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM

COMMENT

Completed

ENTRY

EXPANSION

(Yes/No)

 

 

 

 

 

 

 

 

 

ON/OFF

SERVICE TEST MODE

To Enable Service Test Mode,

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

move Enable/Off/Remote

 

TEST

 

 

 

 

 

 

 

 

 

 

 

 

 

Contact switch to OFF. Change

 

 

 

 

 

 

 

 

TEST to ON. Move switch to

 

 

 

 

 

 

 

 

ENABLE.

 

 

 

 

 

 

 

OUTPUTS AND PUMPS

 

 

 

 

 

 

 

 

 

SIZES 010-018,

 

 

 

 

 

 

 

 

Condenser fan at low speed

 

 

 

 

 

FAN1

ON/OFF

FAN 1 RELAY

SIZES 022-030

 

 

 

ENTER

 

 

 

 

 

Condenser fan A1 energized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIZES 032-055,

 

 

 

 

 

 

 

 

Condenser fan A2 energized

 

 

 

 

 

 

 

 

SIZES 022-030,

 

 

 

 

 

 

 

 

Condenser fan A2 energized

 

 

 

 

 

FAN2

ON/OFF

FAN 2 RELAY

SIZES 032-040,

 

OUTS

 

 

 

Condenser fan B1 at high speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIZES 042-055,

 

 

 

 

 

 

 

 

Condenser fan B2 energized

 

 

 

 

 

CLP.1

ON/OFF

COOLER PUMP 1 RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CLP.2

ON/OFF

COOLER PUMP 2 RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CL.HT

ON/OFF

COOLER/PUMP HEATER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RMT.A

ON/OFF

REMOTE ALARM RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CIRCUIT A COMPRESSOR TEST

 

 

 

 

ENTER

 

CC.A1

ON/OFF

COMPRESSOR A1 RELAY

 

 

CMPA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC.A2

ON/OFF

COMPRESSOR A2 RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MLV

ON/OFF

MINIMUM LOAD VALVE RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CIRCUIT B COMPRESSOR TEST

 

 

 

 

ENTER

 

CC.B1

ON/OFF

COMPRESSOR B1 RELAY

See Note

 

CMPB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC.B2

ON/OFF

COMPRESSOR B2 RELAY

See Note

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MLV

ON/OFF

MINIMUM LOAD VALVE RELAY

See Note

 

 

 

 

 

 

 

 

 

 

NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.

Copyright 2003 Sterling

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

2

PC 903

Catalog No. 533-00047

Printed in U.S.A.

Form 30RA-2T

Pg CL-8

1-03

Replaces: 30RA-1T

Tab

5c

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - CUT ALONG DOTTED LINECUT ALONG DOTTED LINE