Sterling 30RA010-055 manual Legend For Fig

Models: 30RA010-055

1 100
Download 100 pages 44.39 Kb
Page 5
Image 5
LEGEND FOR FIG. 1-6

T10 — REMOTE SPACE TEMPERATURE SENSOR OR DUAL LEAVING WATER TEMPERATURE SENSOR —

One of two inputs can be connected to TB5-5 and TB5-6. See appropriate sensor below.

T10 — Remote Space Temperature Sensor — Sensor T10 (part no. 33ZCT55SPT) is an accessory sensor that is remotely mounted in the controlled space and used for space tempera- ture reset. The sensor should be installed as a wall-mounted thermostat would be (in the conditioned space where it will not be subjected to either a cooling or heating source or direct exposure to sunlight, and 4 to 5 ft above the floor).

Space temperature sensor wires are to be connected to terminals in the unit main control box. The space temperature sensor includes a terminal block (SEN) and a RJ11 female connector. The RJ11 connector is used access into the Sterlco Comfort Network (SCN) at the sensor.

To connect the space temperature sensor (Fig. 9):

1.Using a 20 AWG twisted pair conductor cable rated for the application, connect 1 wire of the twisted pair to one SEN terminal and connect the other wire to the other SEN terminal located under the cover of the space temperature sensor.

2.Connect the other ends of the wires to terminals 5 and 6 on TB5 located in the unit control box.

Units on the SCN can be monitored from the space at the sensor through the RJ11 connector, if desired. To wire the RJ11 connector into the SCN (Fig. 10):

IMPORTANT: The cable selected for the RJ11 connector wiring MUST be identical to the SCN communication bus wire used for the entire network. Refer to Table 5 for acceptable wiring.

1.Cut the SCN wire and strip ends of the red (+), white (ground), and black (–) conductors. (If another wire color scheme is used, strip ends of appropriate wires.)

2.Insert and secure the red (+) wire to terminal 5 of the space temperature sensor terminal block.

3.Insert and secure the white (ground) wire to terminal 4 of the space temperature sensor.

4.Insert and secure the black (–) wire to terminal 2 of the space temperature sensor.

5.Connect the other end of the communication bus cable to the remainder of the SCN communication bus.

T10 — Dual Leaving Water Temperature Sensor — For dual chiller applications (parallel only are supported), connect the dual chiller leaving fluid temperature sensor (5 kther- mistor, Sterling part no. HH79NZ029) to the space temperature input of the Master chiller. If space temperature is required for reset applications, connect the sensor to the Slave chiller and configure the slave chiller to broadcast the value to the Master chiller.

LEGEND FOR FIG. 1-6

ALMR

Alarm Relay

BR

Boiler Relay

CContactor, Compressor

CB

Circuit Breaker

CCB

Compressor Circuit Breaker

CHC

Cooler/Pump Heater Contactor

COMP

Compressor

CWFS

Chilled Water Flow Switch

CWP

Chilled Water Pump

DPT

Discharge Pressure Transducer

EMM

Energy Management

FIOP

factory Installed Option

FM

Fan Motor

GND

Ground

HPS

High-Pressure Switch

HR

Heat Relay

ICP

Inrush Current Protection

IP

Internal Protection Thermostat

LWT

Leaving Water Temperature

MBB

Main Base Board

MLV

Minimum Load Valve

MS

Manual Starter

OAT

Outdoor-Air Thermistor

OL

Overload

RRelay

SPT

Suction Pressure Transducer

SW

Switch

TThermistor

TB

Terminal Block

TNKR

Storage Tank Heater Relay

TRAN

Transformer

 

Terminal Block

 

Terminal (Unmarked)

 

Terminal (Marked)

 

Splice

 

Factory Wiring

 

Field Wiring

 

Accessory or Option Wiring

 

To indicate common potential only;

 

not to represent wiring.

5

Page 5
Image 5
Sterling 30RA010-055 manual Legend For Fig