Sterling 30RA010-055 manual AND MANUAL STARTERS cont, Factory Settings For Compressor, Fan, Pump

Models: 30RA010-055

1 100
Download 100 pages 44.39 Kb
Page 90
Image 90

FACTORY SETTINGS FOR COMPRESSOR, FAN, PUMP,

AND MANUAL STARTERS (cont)

 

 

 

OVERLOAD

OVERLOAD

OVERLOAD

OVERLOAD

 

MANUAL

MANUAL

MANUAL STARTER

 

 

 

MANUAL

 

SETTINGS FOR

UNIT

 

 

RELAY (CA1)

RELAY (CA2)

RELAY (CB1)

RELAY (CB2)

STARTER

STARTER

 

VOLTAGE

VOLTAGE

STARTER

 

PUMP OPTIONS

SIZE

SETTING FOR

SETTING FOR

SETTING FOR

SETTING FOR

SETTING

SETTING

 

V-PH-Hz

SERIES

FOR FANS

 

 

(Model Number

30RA

 

 

COMPRESSOR

COMPRESSOR

COMPRESSOR

COMPRESSOR

FC-HS/LS

FOR

FOR CHC

 

 

Position 9)

 

 

 

A1

A2

B1

B2

 

FC-A1/A2

(Heaters)

 

 

 

 

 

 

 

 

 

 

A/F

B/G

C/H

D/J

E/K

 

 

 

 

 

 

 

 

 

 

032

230-3-50

-800

31.4

40.9

49.9

7.6

4.6

2.5

 

4.8

6.1

10.4

380/415-3-50

-900

17.4

23.8

29

4.6

3.7

1.8

2.9

3.7

6.4

 

 

575-3-60

-100

14.6

19.9

22.7

3.6

2.3

1.8

2.5

3.6

6.0

 

380-3-60

-200

22.7

31.7

36.1

5.5

3.5

1.8

3.7

5.4

9.1

 

230-3-60

-400

35.3

44

52.6

9.1

5.8

2.5

6.2

8.9

15.1

035

208/230-3-60

-500

39.2

49

58.4

10.1

7.0

2.5

7.0

9.8

16.7

 

460-3-60

-600

17.5

24.2

28.6

4.6

2.9

1.8

3.1

4.4

7.6

 

230-3-50

-800

49.9

49.9

49.9

7.6

4.6

2.5

4.8

6.1

10.4

 

380/415-3-50

-900

29

29

29

4.6

3.7

1.8

2.9

3.7

6.4

 

575-3-60

-100

19.9

19.9

22.7

3.6

2.3

1.8

2.5

3.6

6.0

 

380-3-60

-200

31.7

31.7

36.1

5.5

3.5

1.8

3.7

5.4

9.1

040

230-3-60

-400

44

44

52.6

9.1

5.8

2.5

6.2

8.9

15.1

 

208/230-3-60

-500

49

49

58.4

10.1

7.0

2.5

7.0

9.8

16.7

 

460-3-60

-600

24.2

24.2

28.6

4.6

2.9

1.8

3.1

4.4

7.6

042

230-3-50

-800

40.9

40.9

40.9

40.9

4.6

2.5

 

4.8

6.1

10.4

380/415-3-50

-900

23.8

23.8

23.8

23.8

3.7

1.8

2.9

3.7

6.4

 

 

575-3-60

-100

15.5

19.9

15.5

19.9

2.3

1.8

2.5

3.6

6.0

 

380-3-60

-200

24.2

31.7

24.2

31.7

3.5

1.8

3.7

5.4

9.1

 

230-3-60

-400

37.1

44

37.1

44

5.8

2.5

6.2

8.9

15.1

045

208/230-3-60

-500

41.2

49

41.2

49

7.0

2.5

7.0

9.8

16.7

 

460-3-60

-600

19.2

24.2

19.2

24.2

2.9

1.8

3.1

4.4

7.6

 

230-3-50

-800

49.9

49.9

49.9

49.9

4.6

2.5

4.8

6.1

10.4

 

380/415-3-50

-900

29

29

29

29

3.7

1.8

2.9

3.7

6.4

 

575-3-60

-100

19.9

19.9

19.9

19.9

2.3

1.8

2.5

3.6

6.0

 

380-3-60

-200

31.7

31.7

31.7

31.7

3.5

1.8

3.7

5.4

9.1

050

230-3-60

-400

44

44

44

44

5.8

2.5

6.2

8.9

15.1

 

208/230-3-60

-500

49

49

49

49

7.0

2.5

7.0

9.8

16.7

 

460-3-60

-600

24.2

24.2

24.2

24.2

2.9

1.8

3.1

4.4

7.6

 

575-3-60

-100

22.7

22.7

22.7

22.7

2.3

1.8

2.5

3.6

6.0

 

380-3-60

-200

36.1

36.1

36.1

36.1

3.5

1.8

3.7

5.4

9.1

055

230-3-60

-400

52.6

52.6

52.6

52.6

5.8

2.5

6.2

8.9

15.1

 

208/230-3-60

-500

58.4

58.4

58.4

58.4

7.0

2.5

7.0

9.8

16.7

 

460-3-60

-600

28.6

28.6

28.6

28.6

2.9

1.8

 

3.1

4.4

7.6

90

Page 90
Image 90
Sterling 30RA010-055 manual AND MANUAL STARTERS cont, Factory Settings For Compressor, Fan, Pump