OPTIONS

DataPort, DataLink, BAClink Object Definition (cont)

SCN TABLE

DESCRIPTION

STATUS

UNITS

POINT

DataPort

DataLink

BAClink

NAME

 

 

 

 

 

 

 

 

FANS

 

 

 

 

 

 

 

Fan 1 Relay

Off/On

 

FAN_1

RO

RO

RO

 

Fan 2 Relay

Off/On

 

FAN_2

RO

RO

RO

 

Cooler/Pump Heater

Off/On

 

COOL_HTR

RO

RO

NA

 

UNIT ANALOG VALUES

 

 

 

 

 

 

 

Cooler Entering Fluid

snnn.n

°F (°C)

COOL_EWT

RO

RO

RO

 

Cooler Leaving Fluid

snnn.n

°F (°C)

COOL_LWT

RO

RO

RO

 

Lead/Lag Fluid

snnn.n

°F (°C)

DUAL_LWT

RO

RO

NA

 

TEMPERTURE RESET

 

 

 

 

 

 

 

4-20 mA Reset Signal

nn.n

ma

RST_MA

RO

RO

RO

OPTIONS

Outside Air Temperature

snnn.n

°F (°C)

OAT

RO

RW

NA

Space Temperature

snnn.n

°F (°C)

SPT

RO

RW

NA

 

 

DEMAND LIMIT

 

 

 

 

 

 

 

4-20 mA Demand Signal

nn.n

ma

LMT_MA

RO

RO

RO

 

Demand Limit Switch 1

Off/On

 

DMD_SW1

RO

RO

NA

 

Demand Limit Switch 2

Off/On

 

DMD_SW2

RO

RO

NA

 

SCN Loadshed Signal

0, 1, 2

 

DL_STAT

RO

RO

RO

 

MISCELLANEOUS

 

 

 

 

 

 

 

Heat Request

Off/On

 

HEAT_REQ

RO

RO

NA

 

Dual Setpoint Switch

Off/On

 

DUAL_IN

RO

RO

NA

 

Cooler LWT Setpoint

snnn.n

°F (°C)

LWT_SP

RO

RO

NA

 

Ice Done

Off/On

 

ICE_DONE

RO

RO

NA

 

COOLING

 

 

 

 

 

 

 

Cooling Setpoint 1

–20 to 70 (–28.8 to 21.1)

°F (°C)

CSP1

NA

RW

RW

 

Cooling Setpoint 2

–20 to 70 (–28.8 to 21.1)

°F (°C)

CSP2

NA

RW

NA

SETPOINT

Ice Setpoint

–20 to 32 (–28.8 to 0.0)

°F (°C)

CSP3

NA

RW

NA

RAMP LOADING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling Ramp Loading

0.2 to 2.0 (0.1 to 1.1)

dF (dC)

CRAMP

NA

RW

NA

 

Brine Freeze Point

–20 to 34 (–28.8 to 1.1)

°F (°C)

BRN_FRZ

NA

RW

NA

 

Timed Override Hours

0

Hours

OVR-EXT

NA

RW

RW

 

Period 1 DOW (MTWTFSSH)

00000000

 

DOW1

NA

RW

RW

 

Occupied Time

00:00

 

OCCTOD1

NA

RW

RW

 

Unoccupied Time

00:00

 

UNOCTOD1

NA

RW

RW

 

Period 2 DOW (MTWTFSSH)

00000000

 

DOW2

NA

RW

RW

 

Occupied Time

00:00

 

OCCTOD2

NA

RW

RW

 

Unoccupied Time

00:00

 

UNOCTOD2

NA

RW

RW

 

Period 3 DOW (MTWTFSSH)

00000000

 

DOW3

NA

RW

RW

 

Occupied Time

00:00

 

OCCTOD3

NA

RW

RW

 

Unoccupied Time

00:00

 

UNOCTOD3

NA

RW

RW

 

Period 4 DOW (MTWTFSSH)

00000000

 

DOW4

NA

RW

RW

OCCPC01S

Occupied Time

00:00

 

OCCTOD4

NA

RW

RW

Unoccupied Time

00:00

 

UNOCTOD4

NA

RW

RW

 

Period 5 DOW (MTWTFSSH)

00000000

 

DOW5

NA

RW

RW

 

Occupied Time

00:00

 

OCCTOD5

NA

RW

RW

 

Unoccupied Time

00:00

 

UNOCTOD5

NA

RW

RW

 

Period 6 DOW (MTWTFSSH)

00000000

 

DOW6

NA

RW

RW

 

Occupied Time

00:00

 

OCCTOD6

NA

RW

RW

 

Unoccupied Time

00:00

 

UNOCTOD6

NA

RW

RW

 

Period 7 DOW (MTWTFSSH)

00000000

 

DOW7

NA

RW

RW

 

Occupied Time

00:00

 

OCCTOD7

NA

RW

RW

 

Unoccupied Time

00:00

 

UNOCTOD7

NA

RW

RW

 

Period 8 DOW (MTWTFSSH)

00000000

 

DOW8

NA

RW

RW

 

Occupied Time

00:00

 

OCCTOD8

NA

RW

RW

 

Unoccupied Time

00:00

 

UNOCTOD8

NA

RW

RW

LEGEND

NA — Not Available

RO — Read Only

RW — Read/Write

NOTE: In order to write to any point with DataLink or BAClink con- trols, the machine must be configured for SCN control. CTRL Control Method (Configuration mode, sub-mode OPT2) must be set to 3 = SCN Control.