Sterling 30RA010-055 manual Temperature Mode and Sub-ModeDirectory

Models: 30RA010-055

1 100
Download 100 pages 44.39 Kb
Page 29
Image 29
Table 12 — Temperature Mode and Sub-Mode Directory

Table 11 — Service Test Mode and Sub-Mode Directory

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM

COMMENT

ENTRY

EXPANSION

 

 

 

 

TEST

 

 

 

 

ON/OFF

SERVICE TEST MODE

To Enable Service Test Mode,

 

ENTER

 

 

 

 

 

 

 

 

move Enable/Off/Remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Contact switch to OFF. Change

 

 

 

 

 

 

 

TEST to ON. Move switch to

 

 

 

 

 

 

 

ENABLE.

OUTS

 

 

 

 

 

OUTPUTS AND PUMPS

 

 

 

 

FAN1

ON/OFF

FAN 1 RELAY

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN2

ON/OFF

FAN 2 RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

CLP.1

ON/OFF

COOLER PUMP 1 RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

CLP.2

ON/OFF

COOLER PUMP 2 RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

CL.HT

ON/OFF

COOLER/PUMP HEATER

 

 

 

 

 

 

 

 

 

 

 

 

 

RMT.A

ON/OFF

REMOTE ALARM RELAY

 

 

 

 

 

 

 

 

 

CMPA

 

 

 

 

 

CIRCUIT A COMPRESSOR TEST

 

 

 

 

CC.A1

ON/OFF

COMPRESSOR A1 RELAY

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC.A2

ON/OFF

COMPRESSOR A2 RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

MLV

ON/OFF

MINIMUM LOAD VALVE RELAY

 

 

 

 

 

 

 

 

 

CMPB

 

 

 

 

 

CIRCUIT B COMPRESSOR TEST

See Note

 

 

 

CC.B1

ON/OFF

COMPRESSOR B1 RELAY

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CC.B2

ON/OFF

COMPRESSOR B2 RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

MLV

ON/OFF

MINIMUM LOAD VALVE RELAY

 

 

 

 

 

 

 

 

 

NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.

Table 12 — Temperature Mode and Sub-Mode Directory

SUB-MODE

KEYPAD

ITEM

DISPLAY

ITEM

COMMENT

ENTRY

EXPANSION

 

 

 

 

UNIT

 

 

 

 

 

ENT AND LEAVE UNIT TEMPS

 

 

 

 

 

CEWT

XXX.X °F

COOLER ENTERING FLUID

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CLWT

XXX.X °F

COOLER LEAVING FLUID

 

 

 

 

 

 

 

 

 

 

 

 

 

OAT

XXX.X °F

OUTSIDE AIR TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

SPT

XXX.X °F

SPACE TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

DLWT

XXX.X °F

LEAD/LAG LEAVING FLUID

 

 

 

 

 

 

 

 

 

CIR.A

 

 

 

 

 

TEMPERATURES CIRCUIT A

 

 

 

 

SCT.A

XXX.X °F

SATURATED CONDENSING TMP

 

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SST.A

XXX.X °F

SATURATED SUCTION TEMP

 

 

 

 

 

 

 

 

 

 

 

 

 

RGT.A

XXX.X °F

COMPR RETURN GAS TEMP

 

 

 

 

 

 

 

 

 

 

 

 

 

SH.A

XXX.X ^F

SUCTION SUPERHEAT TEMP

 

 

 

 

 

 

 

 

 

CIR.B

 

 

 

 

 

TEMPERATURES CIRCUIT B

See Note

 

 

 

SCT.B

XXX.X °F

SATURATED CONDENSING TMP

See Note

 

 

ENTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SST.B

XXX.X °F

SATURATED SUCTION TEMP

See Note

 

 

 

 

 

 

 

 

 

 

 

 

RGT.B

XXX.X °F

COMPR RETURN GAS TEMP

See Note

 

 

 

 

 

 

 

 

 

 

 

 

SH.B

XXX.X ^F

SUCTION SUPERHEAT TEMP

See Note

 

 

 

 

 

 

 

 

NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.