CIRCBDIO (Circuit B Discrete Inputs/Outputs)
DESCRIPTION | VALUE | UNITS | POINT NAME | FORCEABLE |
CIRC. B DISCRETE OUTPUTS |
|
|
|
|
Compressor B1 Relay | On/Off |
| K_B1_RLY | N |
Compressor B2 Relay | On/Off |
| K_B2_RLY | N |
Minimum Load Valve Relay | On/Off |
| MLV_RLY | N |
|
|
|
|
|
CIRC. B DISCRETE INPUTS |
|
|
|
|
Compressor B1 Feedback | On/Off |
| K_B1_FBK | N |
Compressor B2 Feedback | On/Off |
| K_B2_FBK | N |
CIRCB_AN (Circuit B Analog Parameters)
DESCRIPTION | VALUE | UNITS | POINT NAME | FORCEABLE |
CIRCUIT B ANALOG VALUES |
|
|
|
|
Percent Total Capacity | % | CAPB_T | N | |
Percent Available Cap. | % | CAPB_A | N | |
Discharge Pressure | nnn.n | PSIG | DP_B | N |
Suction Pressure | nnn.n | PSIG | SP_B | N |
Calculated HP Setpoint B | nnn.n | °F | HSP_B | N |
Saturated Condensing Tmp | snnn.n | °F | TMP_SCTB | N |
Saturated Suction Temp | snnn.n | °F | TMP_SSTB | N |
Compr Return Gas Temp | snnn.n | °F | TMP_RGTB | N |
Suction Superheat Temp | snnn.n | ∆F | SH_B | N |
OPTIONS (Unit Parameters)
DESCRIPTION | VALUE | UNITS | POINT NAME | FORCEABLE |
FANS |
|
|
|
|
Fan 1 Relay | Off/On |
| FAN_1 | N |
Fan 2 Relay | Off/On |
| FAN_2 | N |
Cooler/Pump Heater | Off/On |
| COOL_HTR | N |
|
|
|
|
|
UNIT ANALOG VALUES |
|
|
|
|
Cooler Entering Fluid | snnn.n | °F | COOL_EWT | N |
Cooler Leaving Fluid | snnn.n | °F | COOL_LWT | N |
Lead/Lag Leaving Fluid | snnn.n | °F | DUAL_LWT | N |
|
|
|
|
|
TEMPERATURE RESET |
|
|
|
|
nn.n | mA | RST_MA | N | |
Outside Air Temperature | snnn.n | °F | OAT | Y |
Space Temperature | snnn.n | °F | SPT | Y |
|
|
|
|
|
DEMAND LIMIT |
|
|
|
|
nn.n | mA | LMT_MA | N | |
Demand Limit Switch 1 | Off/On |
| DMD_SW1 | N |
Demand Limit Switch 2 | Off/On |
| DMD_SW2 | N |
SCN Loadshed Signal | 0 = Normal |
| DL_STAT | N |
| 1 = Redline |
|
|
|
| 2 = Loadshed |
|
|
|
|
|
|
|
|
MISCELLANEOUS |
|
|
|
|
Heat Request | Off/On |
| HEAT_REQ | N |
Dual Setpoint Switch | Off/On |
| DUAL_IN | N |
Cooler LWT Setpoint | snnn.n | °F | LWT_SP | N |
Ice Done | Off/On |
| ICE_DONE | N |
78