Fig. 13 — Operating Envelope for

Head Pressure Control — The Main Base Board (MBB) controls the condenser fans to maintain the lowest condensing temperature possible, and thus the highest unit efficiency. The MBB uses the saturated condensing tempera- ture input from the discharge pressure transducer to control the fans. Head pressure control is maintained through a calculated set point which is automatically adjusted based on actual

 

160

 

 

 

 

 

 

 

149

 

 

154

 

 

 

 

 

 

 

 

 

 

 

 

140

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

(F)

105

 

 

 

 

 

 

 

 

 

 

 

 

SCT

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

 

78

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

47.5

 

 

 

 

 

 

 

 

 

 

 

 

 

40

 

0

5

10

15

20

 

 

35

40

45

50

55

 

-10

-5

25

30

 

 

 

 

 

 

R-22 SST (F)

 

 

 

 

 

 

LEGEND

SCT — Saturated Condensing Temperature

SST — Saturated Suction Temperature

Fig. 13 — Operating Envelope for

R-22 Maneurop Compressor

saturated condensing and saturated suction temperatures so that the compressor(s) is (are) always operating within the manufacturer's specified envelope (see Fig. 13). The control will automatically reduce the unit capacity as the saturated condensing temperature approaches an upper limit. The control will indicate through an alert that a high ambient unloading mode is in effect. If the saturated condensing temperature in a circuit exceeds the calculated maximum, the circuit will be stopped. For these reasons, there are no head pressure control methods or set points to enter. If the saturated condensing temperature in a circuit is greater than or equal to 95 F (35 C) at start-up, all available condenser fans will be started to prevent excessive discharge pressure during pull-down. The control will turn off a fan stage when the condensing temperature has been below the calculated head pressure set point by 35 F (19.4 C) for more than 2 minutes. Fan sequences are shown in Fig. 14.

MOTORMASTER® V OPTION — For low-ambient opera- tion, the lead fan on a circuit can be equipped with the Motormaster V head pressure controller option or accessory. The control will automatically raise the head pressure set point by 5 F (2.8 C) when Motormaster control is configured. The controller is energized with the first fan stage and adjusts fan speed to maintain a liquid pressure of 135 psig (931 kPa). For sizes 010-018 and Circuit B of sizes 032-040, the two-speed fan is wired for high speed operation and the Motormaster V controller adjusts fan speed. For size 022-030, 042-055 and circuit A of the 032-040 sizes, the lead fan (A1 or B1) in the circuit is controlled. Refer to Fig. 14 for condenser fan staging information. Refer to Fig. 15 for typical pressure transducer location.

FAN ARRANGEMENT

FAN NO.

FAN RELAY

NORMAL CONTROL

 

30RAN010-018

 

 

 

1

FC-LS

Energize Fan at

CONTROL

 

 

 

 

 

Low Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BOX

 

 

 

 

 

1

 

 

1

FC-HS

Energize Fan at

END

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30RAN022-030

 

 

 

1

FC-A1

First Stage

CONTROL

 

 

 

 

 

 

 

Condenser Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BOX

 

 

1

2

 

 

2

FC-A2

Second Stage

END

 

 

 

 

 

 

 

 

 

 

 

 

Condenser Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30RAN032-040

 

 

 

1

FC-A1

On with Compressor A1

 

 

 

 

and/or Compressor A2

CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

FC-A2

First Stage Condenser

BOX

 

 

1

2

 

 

 

 

 

 

Fan, Circuit A

END

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

FC-LS

Low Speed, Fan on

 

 

 

3

 

 

 

w/Compressor B1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

FC-HS

Energize Fan at High Speed,

 

 

 

 

 

 

 

 

 

Circuit B

 

 

 

 

 

 

 

 

 

 

 

 

30RAN042-055

 

 

 

1

FC-A1

On with Compressor A1

 

 

 

 

and/or Compressor A2

CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

FC-A2

First Stage Condenser Fan,

BOX

 

 

 

 

 

 

 

 

 

 

1

2

 

 

Circuit A

END

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

FC-B1

On with Compressor B1

 

 

 

 

 

 

 

 

 

 

 

 

3

4

 

 

and/or Compressor B2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

FC-B2

First Stage Condenser Fan,

 

 

 

 

 

 

 

 

 

Circuit B

 

 

 

 

 

 

 

 

 

 

 

Fig. 14 — 30RA Condenser Fan Sequence

21

Page 21
Image 21
Sterling 30RA010-055 manual Operating Envelope for, R-22Maneurop Compressor, 30RA Condenser Fan Sequence