RESETCON (Temperature Reset and Demand Limit)
DESCRIPTION |
|
| VALUE | DEFAULT | UNITS | POINT NAME |
COOLING RESET |
|
|
|
|
| |
Cooling Reset Type |
| 0 | = No Reset | 0 |
| CRST_TYP |
|
| 1 | = |
|
|
|
|
| 2 | = External temp – OAT |
|
|
|
|
| 3 | = Return Fluid |
|
|
|
|
| 4 | = External temp - SPT |
|
|
|
|
|
|
|
| ||
| 0.0 | ∆F | 420_DEG | |||
|
|
|
|
|
|
|
REMOTE RESET |
|
|
|
|
|
|
Remote – No Reset Temp |
| 0 to 125 | 125.0 | °F | REM_NO | |
Remote – Full Reset Temp |
| 0 to 125 | 0.0 | °F | REM_FULL | |
Remote – Degrees Reset |
| 0.0 | ∆F | REM_DEG | ||
|
|
|
|
|
|
|
RETURN TEMPERATURE RESET |
|
|
|
|
| |
Return – No Reset Temp |
| 0 to 125 | 10.0 | ∆F | RTN_NO | |
Return – Full Reset Temp |
| 0 to 125 | 0.0 | ∆F | RTN_FULL | |
Return – Degrees Reset |
| 0.0 | ∆F | RTN_DEG | ||
|
|
|
|
|
|
|
DEMAND LIMIT |
|
|
|
|
| |
Demand Limit Select |
| 0 | = None | 0 |
| DMD_CTRL |
|
| 1 | = External switch input |
|
|
|
|
| 2 | = |
|
|
|
|
| 3 | = Loadshed |
|
|
|
Demand Limit at 20 mA |
| 0 to 100 | 100 | % | DMT20MA | |
Loadshed Group Number |
| 0 to 99 | 0 |
| SHED_NUM | |
Loadshed Demand Delta |
| 0 to 60 | 0 | % | SHED_DEL | |
Maximum Loadshed Time |
| 0 to 120 | 60 | minutes | SHED_TIM | |
Demand Limit Switch 1 |
| 0 to 100 | 80 | % | DLSWSP1 | |
Demand Limit Switch 2 |
| 0 to 100 | 50 | % | DLSWSP2 |
SCHEDOVR (Timed Override Setup)
DESCRIPTION | VALUE | DEFAULT | UNITS | POINT NAME |
Schedule Number | 0 to 99 | 1 |
| SCHEDNUM |
Override Time Limit | 0 to 4 | 0 | hours | OTL |
Timed Override Hours | 0 to 4 | 0 | hours | OVR_EXT |
Timed Override | No/Yes | No |
| TIMEOVER |
SETPOINT
DESCRIPTION | VALUE | DEFAULT | UNITS | POINT NAME |
COOLING |
|
|
|
|
Cooling Setpoint 1 | 44.0 | °F | CSP1 | |
Cooling Setpoint 2 | 44.0 | °F | CSP2 | |
ICE Setpoint | 32.0 | °F | CSP3 | |
|
|
|
|
|
RAMP LOADING |
|
|
|
|
Cooling Ramp Loading | 0.2 to 2.0 | 1.0 |
| CRAMP |
|
|
|
|
|
Brine Freeze Point | 34.0 | °F | BRN_FRZ |