2 Installation

MIX 56 User Manual

3/8 in. open-end or socket wrench to attach chassis ground wire to ground stud

Wire-wrap tool to attach front cross-connects when used as DSX or to connect DS1 signals to M13 when used as multiplexer

Also, you must supply 14 AWG (minimum) insulated, stranded wire for grounding, and a groundable shielded cable for the ethernet port.

Power

!CAUTION

CAUTION! Do not supply power until all connections are made in accordance with requirements specified in local electrical codes.

ALERT

ALERT! Protect this equipment with a listed/approved branch circuit breaker sufficiently rated to interrupt power at either –48 Vdc at 1 amp, or 24Vdc at 2 amp. The panel must be acces- sible when operating the unit.

The chassis must receive 20Vdc to 60Vdc. Since MIX 56 includes active components, Telect recommends using a dual feed panel to provide input power redundancy.

Technical Support (USA)

By e-mail: getinfo@telect.com

By phone: 888-821-4856 or 509-921-6161

INSPECTION

Compare the contents of the MIX 56 shipping container with the packing list. Call Telect if you are missing anything.

NOTE Telect is not liable for shipping damage.

If the shipping container is damaged, keep it for the carrier’s inspection. Notify the carrier and call Telect’s Customer Service Department:

2-4

Telect, Inc. 122188-10 A0