Telect MIX 56 Installing The Optional Rj Connector Retrofit, Specifications, 2-15, Step Action

Models: MIX 56

1 124
Download 124 pages 12.01 Kb
Page 37
Image 37
INSTALLING THE OPTIONAL RJ CONNECTOR RETROFIT

MIX 56 User Manual

2 Installation

Step Action

1.Verify the power source is unfused.

2.As instructed in the fol- lowing paragraph, con-

nect office battery and

 

 

return (20Vdc to 60Vdc)

+B –B

+A –A

to the screw-down wire-

 

 

binding connectors la-

 

 

belled “A” at either top-

 

 

rear corners of the chas-

 

 

sis. For example, for a

-48V dc plant, connect -48V to -Aand RTN to +A; for a +24V plant, connect +24V to +A and RTN to -A.

Loosen the set screws for each, insert the wires, and tighten the screws.

3.To ensure power redundancy, repeat Step 2 for Side B using a sepa- rate power source. If you are not using a second source, connect Side B to the same source as Side A to avoid triggering an alarm.

4.If a mating connector is used, insert the connector into the recepta- cle and tighten the two screws until the connector is securely in place.

5.Fuse the power source to supply power to the chassis.

INSTALLING THE OPTIONAL RJ CONNECTOR RETROFIT

The optional RJ Connector Retrofit (part # 747-9999-2848) is a one piece unit that converts a system’s wire-wrap pin blocks into 28 RJ-48 connec- tors. To install the unit, you must remove the wire-wrap door and its retain- er clip, and install a mounting post on each side of the pin blocks, as de- scribed on the following pages.

Specifications

Universal Service Order Code (USOC): RJ-48C

Electrical Network Connection: Tip/Ring and Tip1/Ring 1

Mechanical Arrangement: 8-position miniature modular jack

Usage: 1.544 Mb/s digital access lines

122188-10 A0

Telect, Inc.

2-15