Toshiba RAS-10SAVP-E, RAS-B13SKVP-E, RAS-B10SKVP-E service manual Refrigerant Cycle Diagram

Models: RAS-10SAVP-E RAS-B10SKVP-E RAS-B13SKVP-E

1 119
Download 119 pages 48.27 Kb
Page 23
Image 23
7. REFRIGERANT CYCLE DIAGRAM

7. REFRIGERANT CYCLE DIAGRAM

7-1. Refrigerant Cycle Diagram

PPressure measurement

Gauge attaching port

Vacuum pump connecting port

Deoxidized copper pipe Outer dia.:

9.52mm (10SAVP-E, -ND) 9.52mm (13SAVP-E, -ND) 12.7mm (16SAVP-E, -ND) Thickness: 0.8mm

4-way valve (STF-0108Z)

TS

INDOOR UNIT

TCJ

 

 

 

 

 

Indoor heat

T1

Temp. measurement

 

 

 

exchanger

 

 

 

 

TC

heightAllowable

10m:difference

lengthpipeAllowable

 

 

Cross flow fan

TA

Max.

: 25m

 

 

 

 

 

 

 

 

 

 

 

 

 

Min.

: 2m

Deoxidized copper pipe

 

 

 

Chargeless : 15m

Outer dia. : 6.35mm

 

 

 

Charge : 20g/m

Thickness : 0.8mm

 

 

 

 

(16 to 25m)

Sectional shape

 

 

 

 

 

 

of heat insulator

 

 

 

 

 

 

Muffler

 

Strainer

 

 

 

 

Muffler

 

Pulse motor

 

valve at liquid side

 

 

TD

 

(CAM-B22YGTF-3)

 

 

 

Compressor

 

 

DA111A1F-24F

 

 

TO

 

 

Outdoor heat

Split capillary

 

exchanger

 

 

Ø1.2 x 80

 

 

 

 

 

 

Ø1.2 x 80

 

 

 

TE

 

Propeller fan

 

T2 Temp. measurement

 

 

 

 

Refrigerant amount : 1.05kg

OUTDOOR UNIT

NOTE :

Gas leak check position

 

 

 

Refrigerant flow (Cooling)

 

 

 

Refrigerant flow (Heating)

NOTE :

The maximum pipe length of this air conditioner is 25 m. When the pipe length exceeds 15m, the additional charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 200g)

– 23 –

Page 23
Image 23
Toshiba RAS-10SAVP-E, RAS-B13SKVP-E, RAS-B10SKVP-E service manual Refrigerant Cycle Diagram