Toshiba RAS-10SAVP-E, RAS-B13SKVP-E Operation flow and applicable data, etc, Description, Purpose

Models: RAS-10SAVP-E RAS-B10SKVP-E RAS-B13SKVP-E

1 119
Download 119 pages 48.27 Kb
Page 44
Image 44
1.Setting the remote controller

 

Item

 

Operation flow and applicable data, etc.

 

Description

 

 

 

 

 

 

 

 

17. Select switch on

 

 

 

 

 

 

1. Purpose

 

remote controller

 

 

 

 

 

 

This operation is to operate only one

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

indoor unit using one remote controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. Description

 

Push the operation button

 

 

 

 

 

 

 

When operating one indoor unit in a

 

on the remote controller.

 

 

 

situation where two indoor units have

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

been installed in the same room or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nearby rooms, this operation prevents the

 

 

 

 

 

 

 

 

 

remote controller signal from being

 

 

 

 

 

 

 

Select “B” as the setting for

 

Both indoor units

 

YES

 

received simultaneously by both units,

 

 

one of the two indoor units and

 

thus preventing both units from operating.

 

start operation.

 

 

 

for the remote controller.

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

(See below for details.)

 

3. Operation

 

 

 

 

 

 

 

 

The indoor unit on which the remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controller selection has been set to B

 

 

 

 

 

 

 

 

 

Unnecessary set

 

 

 

 

 

receives the signal of the remote control-

 

 

 

 

 

 

ler also set to B.

 

[Remote controller select]

 

 

 

(At the factory the remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

selection is set to A on all the indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

units. There is no A setting display.)

 

 

 

 

 

 

 

 

 

 

HiPOWER

SLEEP MODE

MEMO

 

 

 

 

1.3.5.9H

 

SWING

FIX

FAN

OFF

Jumper wire

CLR

 

 

SET

 

CLOCK

ON

OFF

 

 

 

 

 

 

RESET

 

 

 

 

 

CHECK

 

 

 

Cutting direction

When switching between settings “A” and “B”, always switch the indoor unit board and the remote controller as a pair. (Otherwise, the indoor unit will not accept the remote controller’s signals.)

1.Setting the remote controller

Q Slide and open the remote controller cover and remove the batteries.

R Cut the jumper wire inside the battery compartment using nippers.

The jumper wire should not remain in contact after being cut. Also be careful not to let plastic scraps, jumper wire cuttings or other debris enter the inside of the remote controller.

SInsert the batteries. “B” appears in the remote controller display.

*Even after the jumper wire has been cut, switching between A and B is still possible by pushing the CHECK button and FIX button together.

The A or B setting, which was switched by pushing the CHECK button and FIX button together, is restored to the setting established prior to the switching when the battery is replaced or the RESET button is pushed.

2.Setting the unit

Push the RESET button (Indoor unit) to start automatic operation.

3.Push the 2.Setting the unit button of the remote controller that was set in step 1 to stop the air conditioner.

(This operation will change the setting to “B”.)

4.Check that the remote controller operates the indoor unit.

– 44 –