Image 37
1) Louver position in cooling operation

Item

Operation flow and applicable data, etc.

Description

9. Louver control

This function controls the air direction of the indoor unit.

1) Louver

• The position is automatically controlled according to the operation mode (COOL/HEAT).

position

• The set louver position is stored in memory by the microcomputer, and the louver returns to the

 

 

stored position when the next operation is performed. (Cooling/heating memory position)

 

The angle of the louver is indicated as the horizontal angle is 0°.

When the louver closes fully, it directs approx. 28° upward.

 

Louver angle

Horizontal

1) Louver position in cooling operation

(0˚)

 

Cooling operation/AUTO (COOL)

Powerful

SLEEP MODE operation

Initial setting of “Cooling storage position” “Cooling storage position”

Louver : Directs downward (23˚)

Louver : Directs downward (23˚)

Louver : Directs downward (8˚)

2) Louver position in heating operation

 

 

SLEEP MODE operation

Heating operation/

 

 

In case that the following temp. is

Powerful

In case that the following temp. is obtained

obtained during 12 to 25 minutes from

AUTO (HEAT)

during 12 minutes or 12 to 25 minutes

start of heating operation:

 

 

 

from start of heating operation:

>

 

 

Room temp. (Ta) Set temp. (Tsc) –3.0

 

 

Room temp. (Ta) < Set temp. (Tsc) –3.0

or when 25 minutes or more passed from

 

 

 

start of heating operation

Initial setting of

“Heating storage position”

“Heating storage position”

“Cooling storage position”

“Heating storage position”

Louver :

Louver :

Louver : Directs downward (81˚)

Louver : Directs downward (23˚)

Directs downward (81˚)

Directs downward (81˚)

 

 

 

 

 

3) Louver position in dry operation

Dry operation

Only when the operation frequency is

 

COOL Min–Hz under condition of

 

Room temp. (Ta) < Set temp. (Tsc) +1.0

Initial setting of “Cooling storage position”

Louver : Directs downward (8˚)

 

Louver : Directs downward (23˚)

 

 

 

 

 

 

 

 

 

 

 

 

2) Air direction adjustment

 

 

 

 

 

 

Air direction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal

Inclined

Blowing

Inclined

Horizontal

blowing

blowing

downward

blowing

blowing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3) Swing

• Swing operation is performed in width 35° with the stop position as the

 

 

 

 

center.

 

 

 

• If the stop position exceeds either upper or lower limit position, swing

 

 

 

 

operation is performed in width 35° from the limit which the stop

 

 

 

 

position exceeded.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The louver position can be arbitrarily set up by pushing [FIX] button.

Swing

When pushing [SWING] button during operation, the louver starts swinging.