Toshiba RAS-10SAVP-E, RAS-B13SKVP-E Item, Operation flow and applicable data, etc, Description

Models: RAS-10SAVP-E RAS-B10SKVP-E RAS-B13SKVP-E

1 119
Download 119 pages 48.27 Kb
Page 35
Image 35
<In cooling/dry operation>

Item

6.Release protective control by tempera- ture of indoor heat exchanger

temperature

7˚C

exchanger

6˚C

 

Indoor heat

5˚C

 

temperature

56˚C

exchanger

52˚C

heatIndoor

48˚C

 

Operation flow and applicable data, etc.

Description

<In cooling/dry operation>

 

1) When temperature of the indoor

(Prevent-freezing control for indoor heat exchanger)

heat exchanger drops below 5°C,

the compressor speed is re-

In cooling/dry operation, the sensor of indoor heat

duced. (P zone)

exchanger detects evaporation temperature and controls

2) When temperature of the indoor

the compressor speed so that temperature of the heat

heat exchanger rises in the range

exchanger does not exceed the specified value.

from 6°C to under 7°C, the

 

 

 

 

compressor speed is kept.

 

 

(Q zone)

Usual cooling capacity control

 

3) When temperature of the indoor

 

 

heat exchanger rises to 7°C or

R

 

higher, the capacity control

 

When the value is

operation returns to the usual

 

control in cooling operation.

Q

in Q zone, the

(R zone)

compressor speed

 

is kept.

 

P

 

 

Reduction of compressor speed

 

 

<In heating operation>

 

1) When temperature of the indoor

(Prevent-overpressure control for refrigerating cycle)

heat exchanger rises in the range

from 52°C to 56°C, the compres-

In heating operation, the sensor of indoor heat

sor speed is kept.

exchanger detects condensation temperature and

(Q zone)

controls the compressor speed so that temperature of

When temperature of the indoor

the heat exchanger does not exceed the specified value.

heat exchanger drops in the

 

 

 

 

range from 48°C to under 56°C,

 

 

the compressor speed is kept.

Reduction of compressor speed

 

(Q zone)

P

 

2) When temperature of the indoor

 

 

heat exchanger rises to 56°C or

 

 

higher, the compressor speed is

 

When the value is

reduced. (P zone)

Q

3) When temperature of the indoor

in Q zone, the

 

compressor speed

heat exchanger does not rise to

 

is kept.

52°C, or when it drops below to

 

 

48°C, the capacity control

R

 

operation returns to the usual

 

control in heating operation.

Usual heating capacity control

 

(R zone)

– 35 –

Page 35
Image 35
Toshiba RAS-10SAVP-E, RAS-B13SKVP-E Item, Operation flow and applicable data, etc, Description, <In cooling/dry operation>