Block distinction

Operation of diagnosis function

Check

 

Check

 

Air

 

 

Judgment and action

Block

Cause of operation

conditioner

Remarks

 

code

code

 

 

 

 

status

 

 

 

 

 

 

 

 

 

 

 

Outdoor P.C.

 

Inverter over-current

All off

Displayed when

Even if trying operation again, all

 

board

 

protective circuit

 

error is detected.

operations stop immediately. :

 

 

 

operates. (Short time)

 

 

Replace P.C. board.

 

 

 

Position-detect circuit

All off

Displayed when

1.

Even if connecting lead wire of

 

 

 

error or short-circuit

 

error is detected.

 

compressor is removed, position-

 

 

 

between windings of

 

 

 

detect circuit error occurred. :

 

 

 

compressor

 

 

 

Replace P.C. board.

 

 

 

 

 

 

2.

Measure resistance between

 

 

 

 

 

 

 

wires of compressor, and

 

 

 

 

 

 

 

perform short-circuit. :

 

 

 

 

 

 

 

Replace compressor.

 

 

 

Current-detect circuit

All off

Displayed when

Even if trying operation again, all

 

 

 

error

 

error is detected.

operations stop immediately. :

 

 

 

 

 

 

Replace P.C. board.

 

 

 

Being out of place,

All off

Displayed when

1.

Check sensors (TE, TS).

 

 

 

disconnection or short-

 

error is detected.

2.

Check P.C. board.

 

 

 

circuit of the outdoor

 

 

 

 

 

 

 

heat exchanger sensor

 

 

 

 

 

 

 

(TE) or suction temp.

 

 

 

 

 

 

 

sensor (Ts)

 

 

 

 

 

 

 

Disconnection or short-

All off

Displayed when

1.

Check discharge temp. sensor

 

 

 

circuit of discharge temp.

 

error is detected.

 

(TD).

 

 

 

sensor

 

 

2.

Check P.C. board

 

 

 

Outdoor fan drive system

All off

Displayed when

Position-detect error, over-current

 

 

 

error

 

error is detected.

protective operation of outdoor fan

 

 

 

 

 

 

drive system, fan lock, etc. :

 

 

 

 

 

 

Replace P.C. board or fan motor.

 

Not

 

Being out of place,

Operation

 

1.

Check outdoor temp. sensor

 

displayed

 

disconnection or short-

continues

——

 

(TO).

 

 

 

circuit of the outdoor

 

2.

Check P.C. board.

 

 

 

 

 

 

 

 

temp. sensor (TO)

 

 

 

 

 

Outdoor P.C.

 

Compressor drive output

All off

Displayed when

When 20 seconds passed after

 

board

 

error, Compressor error

 

error is detected.

start-up, position-detect circuit error

 

 

 

(lock, missing, etc.),

 

 

occurred. : Replace compressor.

 

 

 

Break down

 

 

Trouble on P.M.V.

 

Others

 

Return serial signal has

Operation

Flashes when

1.

Repeat Start and Stop with

 

(including

 

been sent when

continues

trouble is detected

 

interval of approx. 10 to 40

 

compressor)

 

operation started, but it

 

on return serial

 

minutes. (Code is not displayed

 

 

 

is not sent from halfway.

 

signal, and normal

 

during operation.)

 

 

 

1) Compressor thermo.

 

status when signal

 

Supply gas.

 

 

 

operation

 

is reset.

 

(Check also gas leak).

 

 

 

Gas shortage

 

 

2.

Unit operates normally during

 

 

 

Gas leak

 

 

 

check.

 

 

 

2) Instantaneous power

 

 

 

If return serial signal does not

 

 

 

failure

 

 

 

stop between indoor terminal

 

 

 

 

 

 

 

block 2 and 3, replace inverter

 

 

 

 

 

 

 

P.C. board.

 

 

 

 

 

 

 

If signal stops between indoor

 

 

 

 

 

 

 

terminal block 2 and 3, replace

 

 

 

 

 

 

 

indoor P.C. board.

 

 

 

Compressor does not

All off

Displayed when

1.

Trouble on compressor

 

 

 

rotate.

 

error is detected.

2.

Trouble on wiring of compressor

 

 

 

(Current protective

 

 

 

(Missed phase)

 

 

 

circuit does not operate

 

 

 

 

 

 

 

when a specified time

 

 

 

 

 

 

 

passed after compressor

 

 

 

 

 

 

 

had been activated.)

 

 

 

 

 

 

 

Discharge temp.

All off

Displayed when

1.

Check dischage temp. sensor

 

 

 

exceeded 117°C

 

error is detected.

 

(TD).

 

 

 

 

 

 

2.

Gas leakage

 

 

 

 

 

 

3.

Trouble on P.M.V.

 

 

 

Break down of

All off

Displayed when

1.

Check power voltage.

 

 

 

compressor

 

error is detected.

 

(220–230–240 V +10%)

 

 

 

 

 

 

2.

Overload operation of refrigera-

 

 

 

 

 

 

 

tion cycle

 

 

 

 

 

 

 

Check installation condition

 

 

 

 

 

 

 

(Short-circuit of outdoor diffuser).

 

 

 

4-way valve inverse error

Operation

 

1.

Check 4-way valve operation.

 

 

 

(TC sensor value

continues

——

 

 

 

 

 

lowered during heating

 

 

 

 

 

 

 

 

 

 

 

 

 

operation.)

 

 

 

 

– 74 –

Page 74
Image 74
Toshiba RAS-10SAVP-E, RAS-B13SKVP-E, RAS-B10SKVP-E service manual Block Cause of operation

RAS-10SAVP-E, RAS-B10SKVP-E, RAS-B13SKVP-E specifications

Toshiba has established itself as a leader in the HVAC market, known for its innovative technologies and reliable performance. Among its range of air conditioning units, the Toshiba RAS-B10SKVP-E, RAS-10SAVP-E, and RAS-B13SKVP-E models stand out for their efficiency and advanced features.

The Toshiba RAS-B10SKVP-E is designed for optimal cooling and heating efficiency, making it an ideal choice for small to medium-sized rooms. One of its main features is the Super Hi-M-PAM inverter technology, which enhances energy savings by continuously adjusting the compressor speed to match the cooling demand. This results in lower energy consumption while maintaining a stable temperature. Additionally, the unit boasts a 4-in-1 operation mode that allows users to select cooling, heating, dehumidification, or ventilating modes, ensuring maximum comfort at all times.

Similarly, the RAS-10SAVP-E model incorporates advanced features such as an eco-friendly refrigerant, R32, which has a lower Global Warming Potential (GWP) compared to traditional refrigerants. This model is equipped with a high-efficiency filter that captures dust and allergens, ensuring cleaner air quality. The sleek design allows for easy integration into various interior styles, while its quiet operation makes it a preferred choice for residential environments.

The RAS-B13SKVP-E model takes performance to the next level with a robust cooling capacity, designed for larger spaces. This model utilizes Toshiba's unique DC Hybrid Inverter technology, which not only enhances cooling efficiency but also facilitates faster temperature control. A notable characteristic of this unit is its wide-angle air distribution system, which allows for even airflow throughout the room, enhancing comfort.

In addition to these features, all three models are equipped with smart controls that enable users to operate their air conditioning systems remotely via mobile devices. This connectivity adds convenience and ensures that users can manage their indoor climate at their fingertips. They also come with user-friendly interfaces and programmable timers, allowing for personalized comfort settings.

In conclusion, the Toshiba RAS-B10SKVP-E, RAS-10SAVP-E, and RAS-B13SKVP-E air conditioning units combine energy efficiency, innovative technology, and user-friendly features to deliver exceptional indoor comfort. With their advanced technologies, these models are ideal choices for anyone seeking reliable and effective climate control solutions.