Toshiba RAS-B13SKVP-E, RAS-B10SKVP-E, RAS-10SAVP-E service manual 33

Models: RAS-10SAVP-E RAS-B10SKVP-E RAS-B13SKVP-E

1 119
Download 119 pages 48.27 Kb
Page 33
Image 33
– 33 –

Item

Operation flow and applicable data, etc.

Description

 

 

 

3. Outdoor fan

The blowing air volume at the outdoor unit side is controlled.

1) The operation command sent

motor control

Receiving the operation command from the controller of

from the remote controller is

 

 

indoor unit, the controller of outdoor unit controls fan speed.

processed by the indoor unit

 

 

* For the fan motor, a DC motor with non-stage variable

controller and transferred to the

 

 

controller of the outdoor unit.

 

 

speed system is used. However, it is limited to 16 stages

 

 

2) When strong wind blows at

 

 

for reasons of controlling.

 

 

 

 

outdoor side, the operation of air

 

 

 

 

conditioner continues with the fan

 

 

 

 

motor stopped.

 

 

 

 

Air conditioner ON

 

 

3) Whether the fan is locked or not

(Remote controller)

 

 

 

 

is detected, and the operation of

 

 

 

 

 

 

air conditioner stops and an

Indoor unit controller

 

 

alarm is displayed if the fan is

 

 

locked.

 

 

 

 

 

 

4) According to each operation

1) Outdoor unit

 

 

mode, by the conditions of

operation command

 

 

outdoor temperature (To) and

(Outdoor fan control)

 

 

compressor revolution, the speed

 

 

 

of the outdoor fan shown in the

 

 

 

table is selected.

2) Fan speed ￿400

YES

OFF status of

 

when the motor stopped.

 

fan motor continues.

 

NO

 

 

 

Fan motor ON

 

 

 

3) Fan lock

YES

Air conditioner

Alarm

 

OFF

display

 

 

NO

 

 

 

4) Motor operates as shown in the table below.

In cooling operation

Compressor speed (rps)

~ 13.8

~ 31.7

32.3 ~ MAX

 

MIN

MAX

MIN

MAX

MIN

MAX

 

 

 

 

 

 

 

 

 

 

 

 

To > 38°C

f 2

f 3

f C

f D

f E

f F

 

 

To > 28°C

f 2

f 3

f B

f C

f E

f F

 

To

To > 15°C

f 2

f 3

f 8

f 9

f A

f B

 

 

To > 5.5°C

f 2

f 3

f 6

f 7

f 8

f 9

 

 

To > 0°C

f 1

f 2

f 4

f 5

f 6

f 7

 

During

To > 38°C

f 2

f 3

f B

f C

f C

f D

 

SLEEP MODE

To < 38°C

f 2

f 3

f 2

f 3

f B

f C

 

When To is abnormal

f D

f F

f D

f F

f D

f F

In Heating operation

Compressor speed (rps)

~16.8

~47.9

48.5 ~ MAX

 

To > 15°C

f 3

f 8

f 9

To

To < 15°C

f 3

f 9

f A

 

 

 

 

To < 5.5°C

f 8

f A

f D

 

 

To < –5.0°C

f B

f C

f D

 

 

 

 

 

 

To > 15°C

f 3

f 3

f 6

During

To < 15°C

f 3

f 3

f 8

SLEEP

 

 

 

 

To < 5.5°C

f 5

f 9

f 9

MODE

 

 

 

 

 

To < –5.5°C

f 7

f A

f B

When To is abnormal

f A

f B

f D

 

 

 

 

 

Outdoor fan speed (rpm)

T ap

10SAVP-E

13SAVP-E

16SAVP-E

10SAVP-ND

13SAVP-ND

16SAVP-ND

 

 

 

 

 

f 1

200

200

200

 

 

 

 

f 2

300

300

300

 

 

 

 

f 3

390

390

390

 

 

 

 

f 4

450

450

450

 

 

 

 

f 5

500

500

500

 

 

 

 

f 6

500

500

500

 

 

 

 

f 7

600

600

650

 

 

 

 

f 8

600

600

650

 

 

 

 

 

 

 

 

 

 

T ap

10SAVP-E

13SAVP-E

16SAVP-E

10SAVP-ND

13SAVP-ND

16SAVP-ND

 

 

 

 

 

 

f 9

700

 

700

750

 

 

 

 

 

f A

700

 

700

750

 

 

 

 

 

f B

700

 

700

750

 

 

 

 

 

f C

700

 

700

750

 

 

 

 

 

f D

750

 

840

920

 

 

 

 

 

f E

750

 

840

920

 

 

 

 

 

f F

750

 

840

920

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 33 –

Page 33
Image 33
Toshiba RAS-B13SKVP-E, RAS-B10SKVP-E, RAS-10SAVP-E service manual 33