Toshiba RAS-B10SKVP-E Item, Operation flow and applicable data, etc, Description, Indoor unit

Models: RAS-10SAVP-E RAS-B10SKVP-E RAS-B13SKVP-E

1 119
Download 119 pages 48.27 Kb
Page 34
Image 34
Remote controller

 

Item

 

 

Operation flow and applicable data, etc.

Description

 

 

 

 

4. Capacity

 

The cooling or heating capacity depending on the load is

1) The difference between set

 

control

 

adjusted.

 

 

 

 

temperature on remote controller

 

 

 

According to difference between the setup value of tempera-

(Ts) and room temperature (Ta)

 

 

 

is calculated.

 

 

 

ture and the room temperature, the capacity is adjusted by

 

 

 

 

 

 

 

the compressor revolution.

2) According to the temperature

 

 

 

 

 

 

 

 

difference, the correction value of

 

Remote controller

 

 

Indoor unit

Hz signal which determines the

 

 

 

 

 

 

 

 

compressor speed is set up.

 

 

Set temp. (Ts)

 

 

Room temp. (Ta)

 

 

 

 

 

 

3) The rotating position and speed

 

of the motor are detected by the

 

electromotive force occurred on

Ts –Ta

the motor winding with operation

 

of the compressor.

Correction of Hz signal

4) According to the difference

resulted from comparison of the

 

 

correction value of Hz signal with

Detection of electromotive force

the present operation Hz, the

inverter output and the commuta-

of compressor motor winding

 

tion timing are varied.

 

 

5) Change the compressor motor

Detection of motor speed and rotor position

speed by outputting power to the

 

 

compressor.

 

 

Correction value of Hz

signal £Operating Hz

* The contents of control

 

 

operation are same in cooling

 

 

operation and heating opera-

Inverter output change

tion

Commutation timing change

 

 

 

 

 

 

Change of compressor speed

 

 

 

 

5. Current release

This function prevents troubles on the electronic parts of the

1) The input current of the outdoor

control

compressor driving inverter.

unit is detected in the inverter

 

This function also controls drive circuit of the compressor

section of the outdoor unit.

 

 

 

speed so that electric power of the compressor drive circuit

2) According to the detected

 

does not exceed the specified value.

outdoor temperature, the

 

 

 

specified value of the current is

Outdoor unit inverter main

Outdoor temp. To

selected.

3) Whether the current value

circuit control current

 

 

exceeds the specified value or

 

 

 

 

 

Setup of current release point

not is judged.

 

 

 

4) If the current value exceeds the

 

 

 

specified value, this function

 

 

NO

reduces the compressor speed

Operating current £Setup value

and controls speed up to the

Reduce compressor speed

closest one commanded from the

 

 

 

YES

 

 

indoor unit within the range which

 

 

 

does not exceed the specified

Capacity control continues.

Current decrease

value.

 

Outdoor temp.

Cooling current

Heating current

 

 

release value

release value

 

 

 

 

 

 

 

 

 

 

 

50°C < TO

6.45A

 

 

 

 

 

 

 

 

45°C < TO < 50°C

7.72A

 

 

 

 

 

 

 

 

 

 

40°C < TO < 45°C

6.75A

 

 

 

 

 

 

 

 

 

 

16°C < TO < 40°C

 

 

 

 

 

 

 

 

 

11°C < TO < 16°C

8.47A

9.22A

 

 

 

 

 

 

 

–5°C < TO < 11°C

 

10.80A

 

 

 

 

 

 

 

TO < –5°C

6.90A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 34 –

Page 34
Image 34