Toshiba RAS-B13SKVP-E, RAS-B10SKVP-E Packed Valve handling precautions, Wiring Connection, 66

Models: RAS-10SAVP-E RAS-B10SKVP-E RAS-B13SKVP-E

1 119
Download 119 pages 48.27 Kb
Page 66
Image 66
Packed Valve handling precautions

Packed Valve handling precautions

Open the valve stem until it touches the stopper. Once it is in contact with the stopper, refrain from applying any more force than is necessary.

Securely tighten the valve stem cap with torque in the following table:

Gas side (Ø12.7 mm)

50 to 62 N•m (5.0 to 6.2 kgf•m)

 

 

Gas side (Ø9.52 mm)

33 to 42 N•m (3.3 to 4.2 kgf•m)

 

 

Liquid side (Ø6.35 mm)

14 to 18 N•m (1.4 to 1.8 kgf•m)

 

 

Service port

14 to 18 N•m (1.4 to 1.8 kgf•m)

 

 

Hexagonal wrench is required.

Fig. 10-4-10

10-4-5. Wiring Connection

1.Remove the valve cover, the electric parts cover and the cord clamp from the outdoor unit.

2.Connect the connecting cable to the terminal as identified by the matching numbers on the terminal block of indoor and outdoor unit.

3.Insert the power cord and the connecting cable fully into the terminal block and secure it tightly with screws.

4.Use vinyl tape, etc. to insulate the cords which are not going to be used. Locate them so that they do not touch any electrical or metal parts.

5.Secure the power cord and the connecting cable with the cord clamp.

6.Attach the electric parts cover and the valve cover on the outdoor unit.

Stripping length of connecting cable

Terminal block

1 2 3 L N

Connecting cable 10-4-5. Wiring Connection Power cord

Fig. 10-4-11

 

 

 

 

 

 

 

 

1

2 3

 

 

L N

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

30

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connecting

 

 

 

 

 

 

 

 

 

 

Earth line

Power cord

Earth line

cable

 

 

 

 

 

 

 

 

 

 

 

Fig. 10-4-12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model RAS-

 

10SAVP-E, 13SAVP-E, 16SAVP-E

 

 

10SAVP-ND, 13SAVP-ND, 16SAVP-ND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power source

 

220 – 240 V ~50 Hz

 

 

 

220 – 220 V ~60 Hz (-E model only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum running

 

 

12.5 A

 

 

current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation fuse

 

 

16 A breaker or fuse

 

 

rating

 

 

 

(All types can be used.)

 

 

 

 

 

 

Power cord

 

 

H07RN-F or 60245IEC66 (1.5 mm²)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connection cable

 

 

Wire type:

 

 

 

H07RN-F or 60245IEC66 (1.0 mm²)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION

Incorrect wiring connection may cause electrical parts to burn out.

Be sure to comply with local regulations/codes when running the wire from outdoor unit to indoor unit.

(Size of wire and wiring method etc.)

Every wire must be securely connected.

If incorrect or incomplete wiring is carried out, fire or smoke may result.

Prepare the power supply for the exclusive use of the air conditioner.

This product can be connected to the main breaker.

Connection to fixed wiring:

A switch or circuit breaker that can disconnect all poles must be included in the fixed wiring.