SYSTem :COMMunicate :SERial[n] :CONTrol :DTR

Example

:COMMunicate :SERial[n] :CONTrol :DTR

Parameters

Comments

Serial communication settings for the Agilent E1324A Datacomm interface can be stored in its on-board non-volatile EEROM only after the DIAG:COMM:SER[n]:STORe command is executed. These settings are used at power-up and DIAG:BOOT[:WARM].

DIAG:BOOT:COLD will set the serial communication parameters to the following defaults:

BAUD 9600

BITS 8

PARity NONE

SBITs 1

DTR ON

RTS ON

PACE XON

Setting baud rate for plug-in card 2.

SYST:COMM:SER2:BAUD 9600

(must be a card number 1 also)

SYSTem:COMMunicate:SERial[n]:CONTrol:DTR < dtr_cntrl> controls the behavior of the Data Terminal Ready output line. DTR can be set to a static state (ON OFF), can operate as a modem control line (STANDard), or can be used as a hardware handshake line (IBFull).

Parameter

Parameter

Range of

Default

Name

Type

Values

Units

 

 

 

 

 

 

 

 

dtr_cntrl

discrete

ON OFF STANDard IBFull

none

The following table defines each value of dtr_cntrl:

Value

Definition

 

 

 

 

ON

DTR line is asserted

 

 

OFF

DTR Line is unasserted

 

 

STANdard

DTR will be asserted when the serial interface is

 

ready to send output data. Data will be sent if the

 

connected device asserts DSR and CTS.

 

 

IBFull

While the input buffer is not yet at the :STOP

 

threshold, DTR is asserted. When the input buffer

 

reaches the :STOP threshold, DTR will be

 

unasserted.

 

 

DIAG:BOOT:COLD will set … DTR to ON.

Related Commands: SYST:COMM:SER[n]:CONT:RTS, SYST:COMM:SER[n]:PACE:THR:STARt, SYST:COMM:SER[n]:PACE:THR:STOP

*RST Condition: No change

Example Asserting the DTR line.

SYST:COMM:SER0:CONT:DTR ON