Panel Calibration

Panel Calibration

This section outlines the steps for calibrating the touch panel. It is recommended that you calibrate the panel both before its initial use and after completing a firmware download.

If it has not already been removed, peel the protective plastic film from the LCD. If the protective plastic film on the LCD is not removed, the panel may not respond properly to touch points on the LCD nor allow proper screen calibration.

Modero panels are factory setup with specific demo touch panel pages. The first splash screen that appears indicates the panel is receiving power, beginning to load firmware, and preparing to display the default touch panel pages. When the panel is ready, the AMX Splash Screen is replaced by the Initial Panel Page.

Calibrating the MVP Panels

1.Press and hold the two lower external pushbuttons on both sides of the MVP (FIG. 8) for 6 seconds to bypass the Setup page and access the Calibrate page (FIG. 9).

3 second press/hold of both buttons: Opens the Setup page

6 second press/hold of both buttons: Opens the Calibrate page

FIG. 8 Location of Setup Access buttons

2.Using the included stylus, press the crosshairs (on the Calibrate page) to set the calibration points on the LCD (FIG. 9).

The request to touch the crosshairs is the first on-screen message

Calibration successful is the second on-screen message that appears after the calibration process is completed

On-screen crosshairs used for

calibration of the touch device

FIG. 9 Calibrate Page

3.After the "Calibration Successful." message appears, press anywhere on the screen to continue and return to the Setup page.

MVP-8400i 8.4" Modero® ViewPoint® Touch Panel with Intercom