2-107
Cisco ONS 15310-CL and Cisco ONS 15310-MA Troubleshooting Guide, R7.0
Chapter2 Alarm Troubleshooting
2.7.165 MANRESET

Clear the MAN-REQ Condition

Step1 Complete the “Initiate a 1+1 Manual Switch Command” procedure on page2-148.
Step2 If the condition does not clear, log into the Technical Support Website at
http://www.cisco.com/techsupport for more information or call CiscoTAC (1-800-553-2447).
2.7.165 MANRESET
Default Severity: NotAlarmed (NA), Non-Service-Affecting (NSA)
SONET Logical Object: EQPT
A User-Initiated Manual Reset condition occurs when you right-click a card in CTC and choose Reset.
Resets performed during a software upgrade also prompt the condition. The MANRESET condition
clears automatically when the card finishes resetting.
Note MANRESET is an informational condition and does not require troubleshooting.
2.7.166 MANSWTOINT
Default Severity: NotAlarmed (NA), Non-Service-Affecting (NSA)
SONET Logical Object: NE-SREF
The Manual Switch To Internal Clock condition occurs when the NE timing source is manually switched
to an internal timing source.
Note MANSWTOINT is an informational condition and does not require troubleshooting.
2.7.167 MANSWTOPRI
Default Severity: NotAlarmed (NA), Non-Service-Affecting (NSA)
SONET Logical Objects: EXT-SREF, NE-SREF
The Manual Switch To Primary Reference condition occurs when the NE timing source is manually
switched to the primary timing source.
Note MANSWTOPRI is an informational condition and does not require troubleshooting.
2.7.168 MANSWTOSEC
Default Severity: NotAlarmed (NA), Non-Service-Affecting (NSA)
SONET Logical Objects: EXT-SREF, NE-SREF