Fluke 434/435

Users Manual

Logger mode

Sampling

Combination of 5 readings/sec and 100/1202 readings/sec continuous sampling

 

per channel depending on the parameter measured

 

 

 

 

 

 

 

 

 

 

 

 

 

Recording time

Depends on selected readings and averaging time

 

 

 

 

 

 

 

 

 

 

 

 

 

Zoom

Two zoom positions, display all or 1x

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Memory

User configurable shared memory, upt to 15 MB on Fluke 435, Up to 7 MB on

 

Fluke 4344

 

 

 

 

 

 

 

Nr of readings on 3

 

1

 

 

10

 

 

100

 

phases + N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Averaging time

0.5 s

10 min

2 hr

0.5 s

10 min

2 hr

0.5 s

10 min

2 hr

 

 

 

 

 

 

 

 

 

 

Max7 duration using

66 hr

9

100

6 hr

333

10

18 min

31

1 year

15MB

 

years

years

 

days

years

 

days

 

 

 

 

 

 

 

 

 

 

 

Measurement

The basic measurement time interval for parameters is a 10/12-cycle time

aggregation over time

interval for 50/60 Hz power systems. Measurement time interval aggregation is

intervals

selected via the Logger averaging time setting.

 

 

 

 

Note: 150/180 cycle (3 s) interval aggregation as per IEC 61000-4-30 Clauses

 

A.7 can be selected from the SETUP, FUNCTION PREF, AGGREGation

 

INTERVAL setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Monitor mode

 

 

 

 

 

 

 

 

 

 

 

Sampling

Combination of 5 readings/sec and 100/1202 readings/sec continuous sampling

 

per channel depending on the parameter measured.

 

 

 

 

 

 

 

 

 

 

Recording time

Up to 1 week with 10 min resoluton

 

 

 

 

 

 

 

 

Memory

1008 min, max and avg points for each reading, 10 minute resolution

 

 

 

 

 

 

 

Limits

According EN50160 or customer definable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

23-10