Specifications23

Electrical Measurements

Power and Energy

Measurement Range

Resolution

Accuracy

 

 

 

 

 

Watt (VA, VAR)

1.0 … 20.00MW1

0.1 … 1 kW1

± 1% ± 10 counts3

Fluke 435

Fluke 434

1.0 … 20.00MW1

0.1 … 1 kW1

± 1.5% ± 10 counts3

kWh6 (kVA6, kVAR6)

00.00 kWhr…200.0

0.01

Xhr….100 Whr1

± 1% ± 10 counts3

 

GWhr1

 

Whr….100 Whr1

± 1.5% ± 10 counts3

 

00.00 kWhr…200.0

0.01

 

GWhr1

 

 

 

Power Factor

0…1

0.01

 

± 0.033

Cos ϕ / DPF

0…1

0.01

 

± 0.033

Flicker

Measurement Range

Resolution

Accuracy

 

 

 

 

Pst (1min), Pst, Plt, PF5

0.00 … 20.00

0.01

Within ±5% of tabulated

instantenous Flicker

 

 

values according

 

 

 

IEC61000-4-15

 

 

 

 

Dc%, Dmax% and Time

0.0 … ± 100.0% for Dc%

0.1% for Dc% and

± 1% for Dc% and

d(t) exceeds limits. As

and Dmax% and 0.000

Dmax% and 10 ms for

Dmax% and 20 ms for

described per IEC

... 9.999s for Time

Time

Time

61000-3-3

 

 

 

 

 

 

 

Unbalance Relative %

Measurement Range

Resolution

Accuracy

 

 

 

 

 

Volts Fluke 435 (neg.

0.0

… 5.0%

0.1%

± 0.15%

and zero seq.)

 

 

 

 

Volts Fluke 434 neg. and

0.0

… 5.0%

0.1%

± 0.5%

zero seq.)

 

 

 

 

 

 

 

 

 

Current (neg. and zero

0.0

… 20%

0.1%

± 1%

seq.)

 

 

 

 

 

 

 

 

 

Unbalance Absolute

Measurement Range

Resolution

Accuracy

 

 

 

 

Fluke 435 Absolute:

0.0 … 1000 Vrms

0.1 Vrms

± 0.05% of nominal

 

 

 

voltage if < 1% of

 

 

 

nominal voltage

 

 

 

± 5% if ≥ 1% of nominal

 

 

 

voltage

Fluke 434 Absolute:

0.0 … 1000 Vrms

0.1 Vrms

± 5% ± 2 counts

 

 

 

 

Arms Absolute:

0.0 … 4000 mV x clamp

1 mVrms x clamp scaling

± 5% ± 5 counts

 

scaling

 

 

 

 

 

 