Fluke 435 Power Quality Main Screen, Parameter Available Bar Graphs Limits Averaging Interval

Models: 435

1 140
Download 140 pages 63.82 Kb
Page 86
Image 86

Fluke 434/435

Users Manual

The table below gives a survey of the aspects of Power Quality Monitoring:

Parameter

Available Bar Graphs

Limits

Averaging Interval

 

 

 

 

V rms

3, one for each phase

Probability 100 %: upper

10 minutes

 

 

& lower limit

 

 

 

Probability x %: upper &

 

 

 

lower limit

 

 

 

 

 

Harmonics

3, one for each phase

Probability 100 %: upper

10 minutes

 

 

limit

 

 

 

Probability x %: upper

 

 

 

limit

 

 

 

 

 

Flicker

3, one for each phase

Probability 100 %: upper

2 Hrs.

 

 

limit

 

 

 

Probability x %: upper

 

 

 

limit

 

 

 

 

 

Dips/Interruptions/Rapid

4, one for each

allowed number of

½ cycle rms based

Voltage Changes/Swells

parameter covering all 3

events per week

 

 

phases

 

 

 

 

 

 

Unbalance

1, covering all 3 phases

Probability 100 %: upper

10 minutes

 

 

limit

 

 

 

Probability x %: upper

 

 

 

limit

 

 

 

 

 

Frequency

1, covering all 3 phases

* Probability 100 %:

10 sec.

 

Measured on Reference

upper & lower limit

 

 

Voltage Input A/L1

Probability x %:

 

 

 

upper & lower limit

 

 

 

 

 

Mains Signaling

6, one for each phase,

* Probability 100 %

3 sec. rms

 

for freq 1 and freq 2

upper limit: N/A

 

 

 

Probability x %:

 

 

 

upper limit: adjustable

 

 

 

 

 

Power Quality Main Screen

To access the Power Quality Main screen:

c

MONITOR

18-4

Page 86
Image 86