Fluke 435 user manual 16-4

Models: 435

1 140
Download 140 pages 63.82 Kb
Page 74
Image 74

Fluke 434/435

Users Manual

Two ways to access Trend:

1.Use the up/down arrow keys to highlight an event in the table. To access Trend press the ENTER key. The Cursor is on, in the mid of screen and located on the selected event.

2.Press Function key F5 to view the Trend part showing the most recent measuring values. Cursor and Zoom can be switched on afterwards when required.

Tips and Hints.

To capture control signals it is essential to know their frequencies in advance. Consult the Internet Website of your local energy supplier for information on what frequencies are used for Mains Signaling in your area.

EN 50160 shows the ‘Meister_Kurve’ for the allowed 3 second average voltage V3s as a function of frequency. Limits should be programmed accordingly.

Voltage level in percent

10

1

 

 

100

0,1

1

10

 

 

Frequency in kHz

 

Figure 16-1. Meister Kurve acc. to EN50160

16-4

Page 74
Image 74
Fluke 435 user manual 16-4