Emergency flash

10.4Emergency flash

If the iRMC S2/S3 firmware can no longer be executed, e.g. because the SDRs are not compatible with the system, then you can use the emergency mode to start the firmware running again. In emergency mode, the system automatically branches to the bootloader and is the ready for the firmware update.

IEmergency mode is indicated by the error LED (global error LED) (rot) and the identification LED (blue) flashing alternately.

To switch the managed server to emergency mode and then update the iRMC S2/S3's firmware, proceed as follows:

ÊDisconnect the power supply connector.

ÊInsert the connector in the socket again with the Identify key held down. The managed server is now in emergency mode.

ÊBoot the server to DOS and use the recovery flash procedure to update the iRMC S2/S3’s firmware.

IIf the firmware is not active then the boot operation may take up to 2 minutes to start. You can ignore the error message “iRMC S2/S3 Controller Error” which the BIOS outputs during this period.