CMS-6R4 Series - User’s Guide

/OFF

Switch Plug(s) Off

Switches selected outlet(s) Off, as described in Section 6.2.2. When a several plugs are switched Off by this command, Boot/Sequence Delay Period will be applied as described in Section 5.5.5.1. The /OFF command can also be entered as /OF.

Note: When this command is executed by a Non-Supervisor, it will only be applied to the plugs that are allowed by the password entered at login.

Availability: Supervisor / Non-Supervisor

Format: /OFF[,Y] <n> [Enter] or /OF[,Y] [Enter]

Where:

,Y

(Optional) Suppresses the Command Confirmation Prompt.

n

The number or name of the plugs that you intend to switch Off.

 

To apply the command to several plugs, enter a space character

 

or plus sign (+) between each plug number. To apply the

 

command to a range of plugs, enter the numbers for the first

 

and last plugs in the range, separated by a colon character (:).

 

To apply the command to all plugs allowed by your password,

 

enter an asterisk character (*).

Response:

Verbose: The CMS-6R4 will list the plugs that will be switched Off, and then display the "Sure? (y/n)" prompt, if Y is entered in response to the prompt, the unit will indicate that the command is in process, and then display the main status screen when complete.

Terse: 5 if Y, unit will respond with K.

Example: Assuming that your password allows access to Plug 2 and Plug 3, to switch Plugs 2 and 3 Off, invoke either one of the following command lines:

/OFF,Y 2+3 [Enter] or /OF,Y 2 3 [Enter]

10-10

Page 108
Image 108
I-Tech Company CMS 6R4 Series manual Switch Plugs Off, Format /OFF,Y n Enter or /OF,Y Enter, 10-10