| TROUBLESHOOTING & REPAIR |
| ||
| Observe Safety Guidelines |
| TROUBLESHOOTING GUIDE | |
| detailed in the beginning of this manual. |
|
| |
|
|
|
| |
| PROBLEMS | POSSIBLE AREAS OF | RECOMMENDED | |
| (SYMPTOMS) | MISADJUSTMENT(S) | COURSE OF ACTION | |
|
|
|
|
|
|
| OUTPUT PROBLEMS |
|
|
| No auxiliary power at receptacles – | 1. If the machine is equipped with | 1. Check the auxiliary power | |
| welding output is normal – engine | circuit breakers, check circuit | receptacles and associated | |
| runs normally. | breakers. Reset if tripped. | wires for loose or faulty con- | |
|
| 2. Make sure the output control | nections. | |
|
|
|
| |
|
| (R1) is set at the maximum | 2. Perform the Auxiliary and | |
|
| position. | Field Winding Voltage Test. | |
|
| 3. Check for loose or faulty plug(s) |
|
|
|
| at the power receptacles. |
|
|
|
|
|
|
|
CAUTION
If for any reason you do not understand the test procedures or are unable to perform the test/repairs safely, con- tact the Lincoln Electric Service Department for electrical troubleshooting assistance before you proceed. Call
RANGER