D. Specifications

1000-A2-GN22-00

 

 

Table D–3. CPX-1000 Electrical Specifications (Continued)

Parameter

Specification

 

 

 

Reference/Comment

 

 

 

Primary power

–48VDC @ 15A, 624W (2480 BTU) from

 

 

plant battery and return. Max. 40A

 

 

surge for < 4 msec on Plant Battery

 

 

supply to shelf at initial power up (20A

 

 

to each supply).

 

 

 

 

 

Shelf circuit breaker rated @ 30A.

 

 

Minimum 14 AWG wires (total of four),

 

 

stranded or solid; up to 40 feet

 

 

maximum from the plant battery

 

 

distribution point.

 

 

 

 

Terminate using LCC or LCD

 

 

 

compression lugs (with two #10 screw

 

 

holes).

 

 

 

 

 

Turn On: 38.5V to

41V

 

 

 

Surge current: 40A (with two power

 

 

supplies installed) at 40 VDC, for

 

 

duration <4 ms

 

 

 

 

 

 

 

Input Voltage

48 Vdc A input and 48 Vdc B input

 

 

 

 

 

 

 

Max power

 

 

 

Estimated, not

15 amps @ 48 Vdc, with a 40A <4 ms

 

surge

 

 

actual

 

 

 

 

Max BTU

1720 BTU/hour

 

 

 

Estimated, not

 

 

 

 

 

actual

Frame Grounding

Stranded copper wire; must be larger

GR-1089-CORE,

 

than the wire size used for –48V power

9.7, R9-17

 

and ground wiring (6 AWG

 

 

 

recommended). Type LCC or LCD two-

 

 

hole compression

lug connection point

 

 

on rear of shelf. Use two 10-32 -in.

 

 

machine screws to secure.

 

 

 

 

 

Input breaker

Magnetic, 50 Amps max. 80 Vdc max.

UL, CSA,VDE

 

 

 

 

 

certified

 

 

 

Electro-static Discharge

banana-style jack, 1 front and 1 rear

 

(ESD) grounding

 

 

 

 

 

 

 

 

 

 

 

System level Electrostatic

 

 

 

×π

GR-1089-CORE,

Discharge

 

 

 

Section 2.0

Alarm output connections

22-gauge solid wire for dry contact

 

 

closures to an external alarm

 

 

 

monitoring system.

 

 

 

 

 

 

 

 

 

D-4

February 2003

Page 152
Image 152
Paradyne CPX-1000 manual Ul, Csa,Vde, Certified