3. Installing the CPX-1000

1000-A2-GN22-00

 

 

 

Note

 

 

 

 

 

Be sure that all grounding connection surfaces are free

 

and clear of contaminants.

 

 

 

 

 

 

 

 

 

Step 3

Set the rear circuit breaker to the Off/0 position (if it is not

 

already off).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Caution

 

 

 

 

 

Make proper polarity connections. Damage may occur to

 

the circuitry when powered up if polarity is reversed.

 

 

 

 

 

 

 

 

 

 

 

 

Step 4

Remove the cover from the plant battery terminal strip.

Step 5

Connect the 48 VDC A and 48 VDC B terminals of the CPX to the

 

48 VDC A and B outputs of the power source using two 14 AWG

 

(or larger), stranded or solid wires terminated in #10 size

 

compression ring lugs (Caltronics #RT-117, or equivalents).

 

 

 

 

 

 

 

Note

 

 

 

 

 

If you use 14 AWG wire, be sure that the plant battery

 

power distribution point is no more than 40 feet from

 

the CPX. Usea larger gaugewire if the power source is

 

further away.

 

 

 

 

Step 6

Connect the Return A and Return B terminals of the CPX to the A

 

(+) and B (+) terminals of the power source as in step 5.

 

 

 

 

 

 

 

Note

 

 

 

 

 

The RTN A and RTN B terminals are also connected

 

 

 

 

 

together inside the CPX enclosure.

 

 

 

 

 

 

 

Step 7

Run the 48V power and battery return wires across the back of

 

each CPX shelf and along the side of the equipment rack, or use the

 

optionalCable Management Assembly.

 

 

 

 