1000-A2-GN22-00

3. Installing the CPX-1000

 

 

Verify

Hardware

Installation

Before attaching cables, take this time to check your work:

Verify that:

Step 1

The 48 VDC A and 48 VDC B terminals of the CPX rear panel are

 

wired to the plant battery 48V A and B branches.

Step 2

The RTN A and RTN B rear terminals are wired to the A (+) and B

 

(+) terminals of the plant battery source.

 

Step 3

Circuit breakers or fuses are installed for the CPX according to site

 

engineering plans at the plant battery branch circuit panel.

Step 4

Using a digital voltmeter, measure that plant battery is 48 VDC at

 

the 48 VDC A and RTN

A (battery return) terminals on the CPX

 

rear panel.

 

Step 5

Measure that plant battery is 48 VDC at the

48 VDC B and

 

 

 

 

RTN B (battery return) terminals.

 

Step 6

Each card is fully seated in its slot on the front plane, and each

 

card’s mounting screws are tight.

 

Step 7

Each transition card (in back of the corresponding card)is firmly

 

seated

in its slot, and each module’s mounting screws are tight.

Step 8

The CPX rack is connected to earth ground.

 

Step 9

Each CPX shelf is connected to rack (frame) ground.

February 2003

3-23

Page 87
Image 87
Paradyne CPX-1000 manual Verify Hardware Installation