System integration

7.1 System requirements

Permissible voltages

The following table shows the permissible line voltages of TN line supply systems for the motors.

Table 7- 1

Permissible line voltages of TN line supply systems, resulting DC link voltages and

 

converter output voltages

 

 

 

 

 

Permissible line

Resulting DC link voltage UZK

Drive output voltage (rms value)

supply voltage

 

 

Uamax

400 V

 

600

V (controlled)

425

V (controlled)

 

 

528

V (uncontrolled)

380

V (uncontrolled)

480 V

 

634

V (uncontrolled)

460

V (uncontrolled)

In combination with the drive system SINAMICS S120, the motors are generally approved for operation on TN and TT networks with grounded neutral and for IT networks. Protective equipment which will shut down the drive system in the event of a ground fault must be provided for motors operated on IT systems.

In operation with a grounded external conductor, an isolating transformer with grounded neutral (secondary side) must be connected between the supply and the drive system to protect the motor insulation from excessive stress.

Requirements

The power unit is selected depending on the motor current at torque M0 and a speed 1 [rev/min] or according to the maximum motor current.

The encoder system used must be harmonized with the particular application.

Drive system

Table 7- 2 Open-loop and closed-loop control systems for the SINAMICS S120 drive system

Closed-loop control

Open-loop control

--

CU-320

SINUMERIK 840D sl

NCU-7x0 / NX1x

SINUMERIK 840Di sl

CU-320

SIMATIC

CU-320

SIMOTION

D4x0 /CX32

Note

Read the corresponding documentation about open-loop and closed-loop control systems.

104

1FW6 Built-in torque motors

Configuration Manual, 05/2009, 6SN1197-0AE00-0BP3

Page 103
Image 103