Configuring the AS-Interface safety monitor
4.3 Creating and changing a configuration
ASIMON V3 - Configuration software for AS-Interface safety monitor
100 Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02
Automatic startIcon
Functional device Automatic start
Parameter
Name: max. 29 ASCII characters plaintext
Input mask
Description
The "automatic start" start device requires no additional start condition. If the AND link for all
monitoring, logic and EDM devices of an OSSD returns the result ON, the "automatic start"
start device releases the OSSD via the respectively configured output device.
Configuration log
Type Designation in the configuration log
80 automatic start
Variants
none
Danger
In the event of an automatic start, the OSSD switches on as soon as all conditions are fulfilled!
The machine can, in this case, start unexpectedly!
Example:
0106 INDEX: 45 = "Name"
0107 TYPE: 80 = automatic start
0108 ASSIGNED: channel one
6
7
8
Note
The combination of the automatic start start device with other start devices is not useful, as
a start would occur in every case.