Configuring the AS-Interface safety monitor
4.3 Creating and changing a configuration
ASIMON V3 - Configuration software for AS-Interface safety monitor
Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02 67
Description
The standard slave monitoring device is used to integrate one bit (input or output) of a non-
safe, standard AS-Interface switching signal as an additional switching signal for operational
switching of the AS-Interface safety monitor relay(s) in an OSSD.
Configuration log
Note
With the input and output bits of a non-safe, standard AS-Interface slave, the process image
is always analysed, i.e. the ON state always means an active signal in the process image.
With the standard slave, the output bits of a slave address can also be used. In this way it is
possible to react to a signal from the controller as well. As of version 2.0 the slaves simulated
by the monitor can also be used for this purpose.
If the Inverted parameter is activated, the inverter icon precedes the icon for the standard sla-
ve device in the configuration.
Notice
The use of a standard slave device for safe switching tasks is not permitted!
Example:
0018 INDEX: 32 = "Name"
0019 TYPE: 23 = activation switch
0020 ASSIGNED: channel one
0021 ADDRESS: 21 BIT: In-0 noninv
8
9
0
1