Configuring the AS-Interface safety monitor
4.3 Creating and changing a configuration
ASIMON V3 - Configuration software for AS-Interface safety monitor
104 Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02
Activation via standard slave
Icon
Functional device Activation via standard slave
Parameter
Name: max. 29 ASCII characters plaintext
Slave type: standard/A/B slave
Address: AS-Interface bus address (1… 31)
Bit address: In-0 … In-3 or Out-0 … Out-3
Input mask
Description
The activation via standard slave start device is used to implement a start function via an
AS-Interface input (Start signal) or an AS-Interface PLC output. Unlike the monitored start -
standard slave start device, this start device is not pulse-sensitive, but rather level-sensitive.
The start signal must be applied for at least 100ms before the device switches to the ON state
and sends the validation request to the output device.
Type Designation in the configuration log
84 enable start standard slave
Variants
none
Danger
Danger! Upon activation via a standard slave, the OSSD switches on as soon as all conditions
are fulfilled and the activating level is reached! When the level is frozen while in the activated
state, the machine can, thus, start unexpectedly!
Note
A combination with the automatic start start device is not permitted.