Commissioning the AS-Interface safety monitor
5.8 Configuration documentation
ASIMON V3 - Configuration software for AS-Interface safety monitor
Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02 153
The configuration log of a faulty configuration contains error entries.
In the above example, line 79 contains the error message indicating that the code table of the
safe AS-Interface slave is faulty. The code "00 00 00 00" indicates that this safe AS-Interface
slave was not switched on (ON state) during the teaching of the safe configuration. Line 115
at the end of the configuration log also contains the error message indicating that the configu-
ration is faulty.
Example configuration log (excerpt) of a faulty configuration
:
:
0075 **************************************************************************5
0076 SUBDEVICE SECTION 6
0077 **************************************************************************7
0078 ADDRESS: 1 used standard 8
0079 ADDRESS: 2 used safety input CODE: 00 00 00 00
**** CONFIG ERROR *********************************
**** error in code
**** CONFIG ERROR *********************************
9
0080 ADDRESS: 3 no entry 0
0081 ADDRESS: 4 no entry 1
:
:
:
0107 ADDRESS: 30 no entry 7
0108 ADDRESS: 31 no entry 8
0109 **************************************************************************9
0110 INFO SECTION 0
0111 **************************************************************************1
0112 INACTIVE: none 2
0113 **************************************************************************3
0114 NOT VALIDATED 4
0115
**** CONFIG ERROR *********************************
**** ERROR IN CONFIGURATION
**** CONFIG ERROR *********************************