Configuring the AS-Interface safety monitor
4.3 Creating and changing a configuration
ASIMON V3 - Configuration software for AS-Interface safety monitor
Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02 61
Configuration log
Example: Synchronisation time 0.3 s, stabilising time 0.2 s, shutdown with test
request
0022 INDEX: 32 = "F1" 2
0023 TYPE: 30 = double channel dependent safety input with filtering
0024 SUBTYPE: no startup test
0025 SUBTYPE: no local acknowledge
0026 ASSIGNED: channel one
0027 SAFE SLAVE: 5
0028 SYNC TIME: 0.300 Sec
0029 STABLE TIME: 0.200 Sec
0030 1-CHANNEL-INTERRUPT TOLERANCE: off
3
4
5
6
7
8
9
0
Example: Synchronisation time infinite, stabilising time 0.2 s, shutdown
without test request
0170 INDEX: 45 = "F2" 0
0171 TYPE: 30 = double channel dependent safety input with filtering
0172 SUBTYPE: no startup test
0173 SUBTYPE: local acknowledge always ADDRESS: 31 BIT: In-0 noninv
0174 ASSIGNED: channel one
0175 SAFE SLAVE: 14
0176 SYNC TIME: infinite
0177 STABLE TIME: 0.200 Sec
0178 1-CHANNEL-INTERRUPT TOLERANCE: delayed test request
0179 TOLERANCE TIME: 0.700 Sec
1
2
3
4
5
6
7
8
9
Example: Synchronisation time infinite, stabilising time 0.2 s, tolerancing
without shutdown
0308 INDEX: 55 = "F3" 8
0309 TYPE: 30 = double channel dependent safety input with filtering
0310 SUBTYPE: startup test
0311 SUBTYPE: local acknowledge ADDRESS: 31 BIT: In-0 invert
0312 ASSIGNED: channel one
0313 SAFE SLAVE: 26
0314 SYNC TIME: infinite
0315 STABLE TIME: 2.000 Sec
0316 1-CHANNEL-INTERRUPT TOLERANCE: delayed switch off
0317!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
0318 !!! ADDITIONAL FAULT DETECTION TIME = 0.600 Sec !!!!!!!!!!!!!!!!!!!!!!!
0319!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
0320 TOLERANCE TIME: 0.600 Sec
9
0
1
2
3
4
5
6
7
8
9
0