Commissioning the AS-Interface safety monitor
5.8 Configuration documentation
ASIMON V3 - Configuration software for AS-Interface safety monitor
152 Programming and Operating Manual, Edition 09/2008, GWA 4NEB 333 1558 02 DS 02
Explanation of the table entries for the AS-Interface bus address assignmentsA provisional configuration log can be identified by the entry "NOT VALIDATED" in line 10Lines 0068 … 0101: Information about the AS-Interface bus
Line 0070 ...
Line 0100:
Table of the AS-Interface bus addresses with designation of
their assignment, see following explanation
Lines 0102 … 0108: Footer information of the configuration log
Line 0104: Designation of inactive slaves
Line 0106: Repetition of the validation information
Line 0107: Designation of configuration log end
no entry No entry present.
not used standard Bus address is occupied by an AS-Interface standard slave which is,
however, not monitored by the AS-Interface safety monitor.
used standard Bus address is occupied by an AS-Interface standard slave which is
monitored by the AS-Interface safety monitor, e.g. local acknowledge-
ment, manual start etc.
not used safety input Bus address is occupied by a safe AS-Interface slave which is, howe-
ver, not monitored by the AS-Interface safety monitor. Also listed is
the code table for this safe AS-Interface slave.
used safety input Bus address is occupied by a safe AS-Interface slave which is moni-
tored by the AS-Interface safety monitor, e.g. emergency shutdown,
contactless active protective device (AOPD), safety guard, safe
AS-Interface output etc. Also listed is the code table for this safe
AS-Interface slave.
Example of a provisional configuration log (excerpt)
0000 **************************************************************************0
0001 CONFIGURATION AS-INTERFACE SAFETY MONITOR 1
0002 IDENT: "Configuration 1" 2
0003 **************************************************************************3
0004 MONITOR SECTION 4
0005 **************************************************************************5
0006 MONITOR VERSION: 02.12 enhanced 6
0007 CONFIG STRUCTURE: 02.01 7
0008 PC VERSION: 02.02 8
0009 DOWNLOAD TIME: 2005/08/05 19:07 9
0010 NOT VALIDATED 0
0011 MONITOR ADDRESS: 28 - 31 DIAGNOSIS: all devices 1
0012 MODE: two independent output groups 2
0013 DIAG FREEZE: no 3
0014 ERROR UNLOCK: no 4
0015 OUTPUT CH1: relais 5
0016 OUTPUT CH2: relais, AS-i CODE: 16 CD A9 E5 6
0017 **************************************************************************5
:
: